| Plan Review Notes For Permit 20010166 |
| Permit Number |
20010166 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-09-22 10:45:25 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | | | | KITCHEN RECEPTACLES. 125-VOLT, SINGLE-PHASE, 15- AND | | | 20-AMPERE RECEPTACLES SHALL HAVE GROUND-FAULT | | | CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. INCLUDING | | | REFIGERATOR, RANGE HOOD ECT. ECT. 210.8(B) (2) |
|