Plan Review Notes
Plan Review Notes For Permit 20010166
Permit Number 20010166
Review Stop B
Sequence Number 2
Notes
Date Text
2020-09-22 09:55:32PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017) EXISTING BUILDING
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED. FBC 107.2.1 ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 2) COMPLIED. PROVIDE (2) SETS OF A COMPLETE FLOOR PLAN
 OF THE BUILDING AND SHOW THE LOCATION OF THE PROPOSED
 WORK. FBC 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED
 AND DRAWN UPON SUITABLE MATERIAL. ELECTRONIC MEDIA
 DOCUMENTS SHALL BE SUBMITTED WHEN APPROVED BY THE
 BUILDING OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 3) COMPLIED. PROVIDE (2) SETS OF A FLOOR PLAN THAT
 SHOWS THE EXISTING CABINET CONFIGURATION. FBC 107.2.1
  
 4) SECOND REQUEST. SPECIFY THE BUILDING OCCUPANCY GROUP
 AND USE ON THE PLANS. FBC 107.3.5 AND 302.1
  
 5) SECOND REQUEST. SPECIFY THE BUILDING'S CONSTRUCTION
 TYPE AND IF IT IS SPRINKLERED. FBC 107.3.5 AND 503
  
 6) SECOND REQUEST. THE CITY DOES NOT HAVE ANY RECORDS
 THAT SHOW AN EXISTING RANGE OR HOOD. THEREFORE, THE
 RANGE AND HOOD WILL BE REVIEWED AS NEW INSTALLATIONS.
 INDICATE THE INTENDED USED OF THE COOKING EQUIPMENT. IS
 IT TO BE USED TO PREPARE MEALS FOR THE STUDENTS AND/OR
 FACULTY, IF SO HOW MANY PEOPLE? PROVIDE THE
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 REQUIREMENTS. FBC 107.2.1.2
  
 7) SECOND REQUEST. A THOROUGH AND COMPLETE PLAN REVIEW
 CANNOT BE COMPLETED AT THIS TIME DUE TO LACK OF
 INFORMATION ON THE SUBMITTED PLANS. ADDITIONAL PLAN
 REVIEW COMMENTS MAY BE GENERATED WHEN MORE INFORMATION
 IS PROVIDED.
  
 8) SECOND REQUEST. WHEN RESUBMITTING, IT IS HELPFUL TO
 PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE CITY RE-SUBMITTAL FORM.
  
 NEW COMMENTS.
  
 9) PLAN SHEET A-1 AND E-1 HAVE A DIFFERENT FLOOR PLAN
 CONFIGURATION AT THE PROPOSED BREAKROOM AREA. PLEASE
 COORDINATE. FBC 107.2.1
  
 10) THE PROPOSED PLANS INDICATE THAT WALLS ARE BEING
 ADDED AND SPACES RECONFIGURED WHICH MAKES THIS IS A
 LEVEL 2 ALTERATION TO AN EXISTING BUILDING. PLEASE NOTE
 THIS ON THE PLANS. FBC EXISTING BUILDING SECTION 501
  
 11) SUBMIT A LIFE SAFETY AND EXITING PLAN.
 THE LIFE SAFETY PLAN NEEDS TO SHOW THE FOLLOWING:
 A) NUMBER OF OCCUPANTS IN EACH AREA FBC 1004.1
 B) CUMULATIVE OCCUPANT LOADS FBC 1004.1.1
 C) EXIT SEPARATION DISTANCE FBC 1015.2.1
 D) COMMON PATH OF EGRESS TRAVEL DISTANCE FBC 1014.3
 E) EXIT ACCESS TRAVEL DISTANCE FBC 1016.3
 F) CLEAR WIDTH OF THE EXIT OR EXIT ACCESS DOORS FBC
 1008.1.1
 G) CAPACITY OF EGRESS DOORS, OCCUPANT LOAD SERVED AND
 MEANS OF EGRESS FACTOR FBC1005.3.2
 H) DISTRIBUTION OF EGRESS CAPACITY FBC1005.5
  
 12) PROVIDE ELEVATIONS OF THE NEW CABINETS IN THE BREAK
 ROOM. DEPENDING ON THE USE OF THE PROPOSED KITCHEN,
 THERE ARE ACCESSIBILITY REQUIREMENTS THAT WILL NEED TO
 BE ADDRESSED. FBC ACCESSIBILITY
  
 13) ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO
 HAVE THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO
 HAVE THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15
  
  
  
  
  