| 2020-01-31 08:02:32 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) EXISTING BUILDING |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) FBC 107.2.1 ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. |
| | |
| | 2) PROVIDE (2) SETS OF A COMPLETE FLOOR PLAN OF THE |
| | BUILDING AND SHOW THE LOCATION OF THE PROPOSED WORK. |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS |
| | SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING |
| | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. |
| | |
| | 3) PROVIDE (2) SETS OF A FLOOR PLAN THAT SHOWS THE |
| | EXISTING CABINET CONFIGURATION. FBC 107.2.1 |
| | |
| | 4) SPECIFY THE BUILDING OCCUPANCY GROUP AND USE ON THE |
| | PLANS. FBC 107.3.5 AND 302.1 |
| | |
| | 5) SPECIFY THE BUILDING'S CONSTRUCTION TYPE AND IF IT |
| | IS SPRINKLERED. FBC 107.3.5 AND 503 |
| | |
| | 6) THE CITY DOES NOT HAVE ANY RECORDS THAT SHOW AN |
| | EXISTING RANGE OR HOOD. THEREFORE, THE RANGE AND HOOD |
| | WILL BE REVIEWED AS NEW INSTALLATIONS. INDICATE THE |
| | INTENDED USED OF THE COOKING EQUIPMENT. IS IT TO BE |
| | USED TO PREPARE MEALS FOR THE STUDENTS AND/OR FACULTY, |
| | IF SO HOW MANY PEOPLE? PROVIDE THE MANUFACTURER'S |
| | SPECIFICATIONS AND INSTALLATION REQUIREMENTS. FBC |
| | 107.2.1.2 |
| | |
| | 7) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE |
| | COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION ON |
| | THE SUBMITTED PLANS. ADDITIONAL PLAN REVIEW COMMENTS |
| | MAY BE GENERATED WHEN MORE INFORMATION IS PROVIDED. |
| | |
| | 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. |
| | |
| | 9) RE-SUBMITTAL PROCEDURE YOU ARE REQUIRED TO FILL OUT |
| | A RE-SUBMITTAL FORM TO BE SUBMITTED WITH THE CORRECTED |
| | PLANS AND/OR OTHER DOCUMENTS. THE PERMIT CLERK WILL |
| | RETRIEVE THE DENIED APPLICATION, PLANS AND OTHER |
| | DOCUMENTS FOR YOU. YOU ARE REQUIRED TO REMOVE THE OLD |
| | PLAN SHEETS THAT HAVE BEEN CORRECTED AND REPLACE THEM |
| | WITH THE NEW ONES. THE CLERK WILL PROVIDE YOU WITH A |
| | STAPLE REMOVER AND A STAPLER. ONE SET OF THE OLD PLAN |
| | SHEETS THAT HAVE BEEN REMOVED SHALL BE MARKED AS VOIDED |
| | AND RESUBMITTED ALONG WITH THE TWO (OR MORE) SETS THAT |
| | CONTAIN THE CORRECTED SHEETS. IF THERE ARE ANY SHEETS |
| | THAT HAVE BEEN STAMPED FOR COUNTY IMPACT FEES, HOA |
| | APPROVAL STAMPS OR OTHERS, RESUBMIT THOSE SHEETS. |
| | IF ALL OF THE PLAN SHEETS HAVE BEEN CORRECTED, THEN TWO |
| | (OR MORE) SETS OF THE NEW PLANS AND ANY OTHER DOCUMENTS |
| | SHALL BE SUBMITTED. |
| | |
| | |
| | |
| | |