Plan Review Notes
Plan Review Notes For Permit 20010166
Permit Number 20010166
Review Stop B
Sequence Number 1
Notes
Date Text
2020-01-31 08:02:32PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017) EXISTING BUILDING
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 2) PROVIDE (2) SETS OF A COMPLETE FLOOR PLAN OF THE
 BUILDING AND SHOW THE LOCATION OF THE PROPOSED WORK.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 3) PROVIDE (2) SETS OF A FLOOR PLAN THAT SHOWS THE
 EXISTING CABINET CONFIGURATION. FBC 107.2.1
  
 4) SPECIFY THE BUILDING OCCUPANCY GROUP AND USE ON THE
 PLANS. FBC 107.3.5 AND 302.1
  
 5) SPECIFY THE BUILDING'S CONSTRUCTION TYPE AND IF IT
 IS SPRINKLERED. FBC 107.3.5 AND 503
  
 6) THE CITY DOES NOT HAVE ANY RECORDS THAT SHOW AN
 EXISTING RANGE OR HOOD. THEREFORE, THE RANGE AND HOOD
 WILL BE REVIEWED AS NEW INSTALLATIONS. INDICATE THE
 INTENDED USED OF THE COOKING EQUIPMENT. IS IT TO BE
 USED TO PREPARE MEALS FOR THE STUDENTS AND/OR FACULTY,
 IF SO HOW MANY PEOPLE? PROVIDE THE MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION REQUIREMENTS. FBC
 107.2.1.2
  
 7) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION ON
 THE SUBMITTED PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED WHEN MORE INFORMATION IS PROVIDED.
  
 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
 9) RE-SUBMITTAL PROCEDURE YOU ARE REQUIRED TO FILL OUT
 A RE-SUBMITTAL FORM TO BE SUBMITTED WITH THE CORRECTED
 PLANS AND/OR OTHER DOCUMENTS. THE PERMIT CLERK WILL
 RETRIEVE THE DENIED APPLICATION, PLANS AND OTHER
 DOCUMENTS FOR YOU. YOU ARE REQUIRED TO REMOVE THE OLD
 PLAN SHEETS THAT HAVE BEEN CORRECTED AND REPLACE THEM
 WITH THE NEW ONES. THE CLERK WILL PROVIDE YOU WITH A
 STAPLE REMOVER AND A STAPLER. ONE SET OF THE OLD PLAN
 SHEETS THAT HAVE BEEN REMOVED SHALL BE MARKED AS VOIDED
 AND RESUBMITTED ALONG WITH THE TWO (OR MORE) SETS THAT
 CONTAIN THE CORRECTED SHEETS. IF THERE ARE ANY SHEETS
 THAT HAVE BEEN STAMPED FOR COUNTY IMPACT FEES, HOA
 APPROVAL STAMPS OR OTHERS, RESUBMIT THOSE SHEETS.
 IF ALL OF THE PLAN SHEETS HAVE BEEN CORRECTED, THEN TWO
 (OR MORE) SETS OF THE NEW PLANS AND ANY OTHER DOCUMENTS
 SHALL BE SUBMITTED.
  
  
  
  