Plan Review Notes
Plan Review Notes For Permit 20010152
Permit Number 20010152
Review Stop M
Sequence Number 1
Notes
Date Text
2020-01-16 08:32:191ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20010152
 1/16/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO MECHANICAL PLANS HAVE BEEN SUBMITTED. PLEASE
 CLARIFY IF ANY ALTERATIONS TO THE EXISTING HVAC SYSTEMS
 ARE PROPOSED SUCH AS KITCHEN AND BATH EXHAUST SYSTEMS,
 AC SYSTEM REPLACEMENTS, OR DUCT ALTERATIONS- SECTION
 107.2.1 WPB. PLEASE NOTE THAT MECHANICAL EXHAUST IS
 REQUIRED FOR THE BATHS AT AN INTERMITTENT RATE OF 50
 CFMS, AND FOR THE KITCHENS AT AN INTERMITTENT RATE OF
 100 CFMS- TABLE 403.3.1.1 FBC M.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL NEW
 COOKING APPLIANCES AND KITCHEN HOODS- SECTIONS 505 AND
 917.2 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved