| 2020-01-29 18:58:56 | RESIDENTIAL (R2) ALTERATION BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE. |
| | |
| | 1- THIS IS TYPE I CONSTRUCTION FIRE SPRINKLERED |
| | BUILDING. THE SCOPE OF WORK INCLUDES THE REMOVAL OF |
| | WALLS AND CEILINGS. NEW DROPPED CEILINGS ARE PROPOSED. |
| | PLANS DON'T PROVIDE ANY INFORMATION HOW THE PROPOSED |
| | WORK WILL AFFECT THE EXISTING FIRE SPRINKLER SYSTEM. |
| | PROVIDE SCHEMATIC LAYOUT SHOWING HOW THE FIRE SPRINKLER |
| | SYSTEM WILL BE AFFECTED. SEC. 801.3 FBC-EXISTING |
| | BUILDING. SEC. 107.3.5.1.1 CITY AMENDMENTS. |
| | NOTE: SEPARATE PERMITS ARE REQUIRED FOR FIRE SPRINKLERS |
| | AND FIRE ALARMS. |
| | |
| | 2- PLANS SUBMITTED SEEM TO HAVE A COPY OF THE |
| | ARCHITECT'S SIGNATURE. ALL PLANS NEED TO BE PERSONALLY |
| | SIGNED BY THE ARCHITECT OF RECORD (NO COPIES) AS |
| | REQUIRED BY 61G1-16.003 FLORIDA ADMINISTRATIVE CODE |
| | WHEN SUBMITTING PLANS FOR PUBLIC RECORDS. |
| | ARCHITECT TO PROVIDE SIGNATURE AND DATE ON ALL |
| | DRAWINGS. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY.(NOTE: SUBMIT OLD DRAWINGS FOR REFERENCE) A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |