2020-01-29 18:58:56RESIDENTIAL (R2) ALTERATION BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1- THIS IS TYPE I CONSTRUCTION FIRE SPRINKLERED
 BUILDING. THE SCOPE OF WORK INCLUDES THE REMOVAL OF
 WALLS AND CEILINGS. NEW DROPPED CEILINGS ARE PROPOSED.
 PLANS DON'T PROVIDE ANY INFORMATION HOW THE PROPOSED
 WORK WILL AFFECT THE EXISTING FIRE SPRINKLER SYSTEM.
 PROVIDE SCHEMATIC LAYOUT SHOWING HOW THE FIRE SPRINKLER
 SYSTEM WILL BE AFFECTED. SEC. 801.3 FBC-EXISTING
 BUILDING. SEC. 107.3.5.1.1 CITY AMENDMENTS.
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR FIRE SPRINKLERS
 AND FIRE ALARMS.
  
 2- PLANS SUBMITTED SEEM TO HAVE A COPY OF THE
 ARCHITECT'S SIGNATURE. ALL PLANS NEED TO BE PERSONALLY
 SIGNED BY THE ARCHITECT OF RECORD (NO COPIES) AS
 REQUIRED BY 61G1-16.003 FLORIDA ADMINISTRATIVE CODE
 WHEN SUBMITTING PLANS FOR PUBLIC RECORDS.
 ARCHITECT TO PROVIDE SIGNATURE AND DATE ON ALL
 DRAWINGS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY.(NOTE: SUBMIT OLD DRAWINGS FOR REFERENCE) A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,