| Plan Review Notes For Permit 20010135 |
| Permit Number |
20010135 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-01-08 09:41:03 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #20010135 | | | 1/8/20 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE ORIGINAL PLANS FOR THE PROPOSED PROJECT WERE | | | SUBMITTED ELECTRONICALLY UNDER PERMIT #19070067. THE | | | REVISED PLANS ARE PAPER SUBMITTALS THAT DO DO BEAR THE | | | ENGINEER'S SIGNATURE AND SEAL AS REQUIRED BY FL. | | | STATUTE 471.025 AND SECTION 61G15-23.002 FLORIDA | | | ADMINISTRATIVE CODE. PLEASE RESUBMIT THE REVISED PLANS | | | ELECTRONICALLY. | | | | | | 2) THE REVISION APPLICATION INDICATES 37 NEW VAV BOXES, | | | HOWEVER THE PLANS ARE INDICATING 20. PLEASE CLARIFY. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|