| Plan Review Notes For Permit 20010127 |
| Permit Number |
20010127 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-01-06 15:02:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE PROPOSED AREA IS NOT DESIGNED FOR ASSEMBLY | | | OCCUPANCY. | | | | | | A DETAILED LIFE SAFETY PLAN IS REQUIRED THAT INCLUDES, | | | TOTAL PROPOSED OCCUPANCY AND HOW IT WILL BE CONTROLLED, | | | EXIT DOORS AND EXIT TRAVEL DISTANCES, EMERGENCY | | | LIGHTING, EXIT PATH LIGHTING, EXIT LIGHTS, SEATING | | | AISLES WIDTH, ETC. | | | | | | | | | | | | 2) A STAGE IS INDICATED - WHAT IS THE PURPOSE OF THE | | | STAGE, HOW WILL IT BE CONSTRUCTED, WHERE WILL IT BE | | | LOCATED WITH AN ACTUAL FLOOR/ROOF LAYOUT PLAN? | | | | | | | | | | | | 3) THERE ARE TWO LOUNGE AREAS INDICATED - WHAT DO THERE | | | AREAS CONSIST OF? WHAT ARE THE SIZES? PROVIDE A | | | DETAILED FLOOR/SITE PLAN SHOWING DIMENSIONS TO | | | WALLS/DOORS ETC. | | | | | | PROVIDE DETAILS | | | | | | | | | | | | 4) ROUND OBJECTS ARE INDICATED, WHAT ARE THESE ROUND | | | OBJECTS? | | | | | | PROVIDE DETAILS | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|