Plan Review Notes
Plan Review Notes For Permit 20010107
Permit Number 20010107
Review Stop P
Sequence Number 3
Notes
Date Text
2020-04-01 11:38:211) SHT. A-202 - SEC. 611.2 OF THE FBC-ACCESS.CLEARLY
 STATES A CLEAR FLOOR SPACE POSITIONED FOR A PARALLEL
 APPROACH SHALL BE PROVIDED BUT THE PLANS SHOW A FORWARD
 APPROACH.REVISE THE PLAN.
 2) SUBMIT A RISER DIAGRAM THAT COMPLIES WITH THE
 PLUMBING CODE. WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 3) THE DRAIN AND STACK FOR THE WASHING MACHINE SHALL BE
 3 INCHES IN DIAMETER PER FBC-PLUMBING SEC.406.2.
 4) THE ACCESSIBLE SHOWER/BATHTUB SPECS STILL SHOW
 VERTICAL GRAB BARS IN THE UNIT. CLARIFY.
 5) SHT. A-503 - THE LAVATORY CANNOT ENCROACH INTO THE
 CLEAR FLOOR SPACE FOR THE WATER CLOSET UNLESS THE WATER
 CLOSET CLEAR FLOOR UNLESS THE CLEARANCE FOR THE WATER
 CLOSET IS 66 INCHES MINIMUM MEASURED PERPENDICULAR FROM
 THE REAR WALL. THE PLAN SHOWS THE WATER CLOSET
 CLEARANCE AS 50 INCHES BY 60 INCHES.
 6) SHTS. A-401, A-402, A-403 & A-404 HAS A NOTE STATING
 THE CONDENSATE WILL DISCHARGE A MINIMUM OF ONE FOOT
 FROM THE EXTERIOR WALL AND ALSO A NOTE STATING THE
 CONDENSATE WILL DISCHARGE A MINIMUM OF 2 INCHES FROM
 THE EXTERIOR WALL. REMOVE THE NOTE REFERENCING THE 2
 INCHES.
 7) THE SUBMITTED SPEC SHEET FOR THE TUB /SHOWER GIVES
 NO INFORMATION ON THE TUB SEAT MEASUREMENTS.SUBMIT
 ADDITIONAL SPECS THAT SHOW COMPLIANCE WIRG FBC-ACCESS
 SEC.610.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  