| 2020-04-01 11:38:21 | 1) SHT. A-202 - SEC. 611.2 OF THE FBC-ACCESS.CLEARLY |
| | STATES A CLEAR FLOOR SPACE POSITIONED FOR A PARALLEL |
| | APPROACH SHALL BE PROVIDED BUT THE PLANS SHOW A FORWARD |
| | APPROACH.REVISE THE PLAN. |
| | 2) SUBMIT A RISER DIAGRAM THAT COMPLIES WITH THE |
| | PLUMBING CODE. WPB AMEND. TO FBC SEC. 107.3.5.1.3. |
| | 3) THE DRAIN AND STACK FOR THE WASHING MACHINE SHALL BE |
| | 3 INCHES IN DIAMETER PER FBC-PLUMBING SEC.406.2. |
| | 4) THE ACCESSIBLE SHOWER/BATHTUB SPECS STILL SHOW |
| | VERTICAL GRAB BARS IN THE UNIT. CLARIFY. |
| | 5) SHT. A-503 - THE LAVATORY CANNOT ENCROACH INTO THE |
| | CLEAR FLOOR SPACE FOR THE WATER CLOSET UNLESS THE WATER |
| | CLOSET CLEAR FLOOR UNLESS THE CLEARANCE FOR THE WATER |
| | CLOSET IS 66 INCHES MINIMUM MEASURED PERPENDICULAR FROM |
| | THE REAR WALL. THE PLAN SHOWS THE WATER CLOSET |
| | CLEARANCE AS 50 INCHES BY 60 INCHES. |
| | 6) SHTS. A-401, A-402, A-403 & A-404 HAS A NOTE STATING |
| | THE CONDENSATE WILL DISCHARGE A MINIMUM OF ONE FOOT |
| | FROM THE EXTERIOR WALL AND ALSO A NOTE STATING THE |
| | CONDENSATE WILL DISCHARGE A MINIMUM OF 2 INCHES FROM |
| | THE EXTERIOR WALL. REMOVE THE NOTE REFERENCING THE 2 |
| | INCHES. |
| | 7) THE SUBMITTED SPEC SHEET FOR THE TUB /SHOWER GIVES |
| | NO INFORMATION ON THE TUB SEAT MEASUREMENTS.SUBMIT |
| | ADDITIONAL SPECS THAT SHOW COMPLIANCE WIRG FBC-ACCESS |
| | SEC.610.2. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |