Plan Review Notes
Plan Review Notes For Permit 20010107
Permit Number 20010107
Review Stop P
Sequence Number 1
Notes
Date Text
2020-01-30 13:55:041) THE WASHERS AND DRYERS SHALL COMPLY WITH FBC-ACCESS.
 SEC.611.1 THRU 611.4. SHOW COMPLIANCE ON THE PLANS.
 2) SHT. A4.01 - CONDENSATE LINES SHALL DISCHARGE A
 MINIMUM OF ONE FOOT FROM THE EXTERIOR WALL PER
 FBC-BUILDING SEC. 1503.7.
 3) SUBMIT MANUFACTURER'S DETAILS ON THE REMOVEABLE TUB
 SEAT. THE SEAT SHALL COMPLY WITH FBC-ACCESS. SEC.610.2.
 4) SHT. A5.01 - NOTE #18 - THE GRAB BARS SHALL BE
 MEASURED FROM THE FINISH FLOOR TO THE TOP OF THE
 GRIPPING SURFACE. FBC-ACCESS. SEC.609.4.
 5) SHT. A5.01 - NOTE #5 - THE HEIGHT OF THE ACCESSIBLE
 WATER CLOSET SHALL BE MEASURED TO THE TOP OF THE SEAT,
 NOT THE RIM OF THE WATER CLOSET. FBC-ACCESS. SEC.604.4.
 6) SHT. A5.01 SHOWS VERTICAL GRAB BARS TO BE INSTALLED.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION
 PER FBC-ACCESS. SEC. 609.4.
 7) SHT.A5.03 - DETAIL #2 SHOWS A PROPOSED ACCESSIBLE
 FLOOR PLAN BUT THE FLOOR PLAN SHOWS THE LAVATORY
 ENCROACHING INTO THE CLEAR FLOOR SPACE FOR THE WATER
 CLOSET.CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  