| 2020-02-07 15:13:35 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #20010107 |
| | 2/7/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE LABEL THE A601, 701, 702, & 703 |
| | (ARCHITECTURAL) PLANS THAT ARE MECHANICAL AS "M" PLANS- |
| | SECTION 107.2.1 WPB. |
| | |
| | 2) FULL COMPLIANCE WITH THE FLORIDA ENERGY CODE- 2017 |
| | IS REQUIRED BECAUSE THE PREVIOUSLY UNCONDITIONED |
| | APARTMENTS ARE NOW BEING CONDIITONED WITH NEW HEAT PUMP |
| | SYSTEMS- REFER TO SECTIONS C503.2 & C101.5 FBC EC. |
| | |
| | 3) PROVIDE REFRIGERANT PIPING RISER DRAWINGS, AND SHOW |
| | CONSTRUCTION DETAILS FOR THE EXTERIOR CHASES- SECTION |
| | 107.2.1 WPB. PLEASE INCLUDE A UL TESTED FIRESTOPPING |
| | ASSEMBLY DETAIL- SECTION 714.3.1.1 FBC B. |
| | |
| | 4) SHEET A601: PROVIDE THE HSPF FOR THE HEAT PUMPS IN |
| | THE EQUIPMENT SCHEDULE- SEE TABLE C403.2.3(2) FBC EC. |
| | |
| | 5) A703: REFER TO SECTION 1510.10 AND TABLE 1510.10 FBC |
| | B AND PROVIDE THE CLEARANCE DISTANCE BETWEEN THE ROOF |
| | SURFACE AND THE UNDERSIDE OF THE CONDENSER. |
| | |
| | 6) A703: PROVIDE CONDENSATE DISPOSAL RISER DRAWINGS |
| | THAT SHOW THE TYPES AND SIZES OF CONDENSATE PIPINGS, |
| | PIPING RUNS AND DISHARGE LOCATIONS- SECTION 307.2.1 FBC |
| | M. PLEASE REMOVE THE NOTE INDICATING DISCHARGE INTO |
| | NEARST P-TRAP. CONDENSATE SHALL NOT DISCHARGE INTO THE |
| | WPB SANITARY SYSTEM- SECTION 90-126. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK "VOID" OR "OLD" ON THEM. PLEASE |
| | RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. |
| | THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |