| 2020-01-14 16:21:27 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET G 001 - THERE IS NO CODE REFERENCE INDICATING |
| | REVIEW NOR COMPLIANCE WITH THE FLORIDA FIRE PREVENTION |
| | CODE, 6TH ED. |
| | |
| | PLEASE REVIEW AND ENSURE COMPLAINCE AND ADD THE CODE |
| | REFERENCE. |
| | |
| | |
| | |
| | |
| | 2) THE IS NO LIFE SAFETY PLAN. |
| | |
| | PER NFPA 1 |
| | |
| | 4.1.3.2.2.3 BUILDINGS SHALL BE DESIGNED AND CONSTRUCTED |
| | TO PROVIDE |
| | REASONABLE LIFE SAFETY FOR OCCUPANTS AND WORKERS DURING |
| | CONSTRUCTION AND DEMOLITION. |
| | |
| | 4.1.3.2.2.4 BUILDINGS SHALL BE DESIGNED AND CONSTRUCTED |
| | TO PROVIDE |
| | REASONABLE NOTIFICATION TO OCCUPANTS OF FIRE AND OTHER |
| | EMERGENCY |
| | SITUATIONS. |
| | 4.1.3.2.2.5 BUILDINGS SHALL BE DESIGNED AND CONSTRUCTED |
| | TO PROVIDE |
| | REASONABLE SIGNAGE AND LIGHTING TO IDENTIFY HAZARDS, |
| | EXITS, MEANS |
| | OF EGRESS, AND OTHER BUILDING SAFETY FEATURES. |
| | |
| | |
| | WILL THE BUILDING REMIAN OCCUPIED DURING DEMO AND |
| | RECONSTRUCTION? HOW WILL THE EXITS AND TRAVEL PATHS BE |
| | MAINTAINED AT ALL TIMES.? |
| | |
| | 4.5.6 CONSTRUCTION, REPAIR, AND IMPROVEMENT OPERATIONS. |
| | 4.5.6.1 BUILDINGS OR PORTIONS OF BUILDINGS SHALL BE |
| | PERMITTED TO BE |
| | OCCUPIED DURING CONSTRUCTION, REPAIR, ALTERATIONS, OR |
| | ADDITIONS ONLY |
| | WHERE REQUIRED MEANS OF EGRESS AND REQUIRED FIRE |
| | PROTECTION |
| | FEATURES ARE IN PLACE AND CONTINUOUSLY MAINTAINED FOR |
| | THE PORTION |
| | OCCUPIED OR WHERE ALTERNATIVE LIFE SAFETY MEASURES AND |
| | BUILDING |
| | PROTECTION MEASURES ACCEPTABLE TO THE AHJ ARE IN PLACE. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS FOR DEMO AND |
| | RECONSRTRUCTION. |
| | |
| | |
| | |
| | 3) THERE ARE NO INDICAZTIONS OF WHETHER THIS BUILDING |
| | HAS A FIRE SPRINKLER OR FIRE ALARM SYSTEM. |
| | |
| | PER NFPA 101 |
| | |
| | 31.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 31.3.4.1 GENERAL. |
| | 31.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN |
| | HEIGHT OR WITH |
| | MORE THAN 11 DWELLING UNITS, OTHER THAN THOSE MEETING |
| | THE REQUIREMENTS |
| | OF 31.3.4.1.2, SHALL BE PROVIDED WITH A FIRE ALARM |
| | SYSTEM IN ACCORDANCE |
| | WITH SECTION 9.6, EXCEPT AS MODIFIED BY 31.3.4.2 |
| | THROUGH 31.3.4.5. |
| | |
| | 31.3.4.5 SMOKE ALARMS. |
| | 31.3.4.5.1* IN BUILDINGS OTHER THAN THOSE EQUIPPED |
| | THROUGHOUT WITH AN |
| | EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM, |
| | SMOKE ALARMS |
| | SHALL BE INSTALLED IN ACCORDANCE WITH 9.6.2.10, AS |
| | MODIFIED BY 31.3.4.5.2, |
| | OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY |
| | OF THE BEDROOMS |
| | AND ON ALL LEVELS OF THE DWELLING UNIT, INCLUDING |
| | BASEMENTS. |
| | 31.3.4.5.2 SMOKE ALARMS REQUIRED BY 31.3.4.5.1 SHALL |
| | NOT BE REQUIRED TO |
| | BE PROVIDED WITH A SECONDARY (STANDBY) POWER SOURCE. |
| | 31.3.4.5.3 IN BUILDINGS OTHER THAN THOSE EQUIPPED |
| | THROUGHOUT WITH AN |
| | EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM OR |
| | A COMPLETE, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH 31.3.5, |
| | SMOKE ALARMS SHALL BE INSTALLED IN EVERY SLEEPING AREA |
| | IN |
| | ACCORDANCE WITH 9.6.2.10, AS MODIFIED BY 31.3.4.5.4. |
| | 31.3.4.5.4 SMOKE ALARMS REQUIRED BY 31.3.4.5.3 SHALL BE |
| | PERMITTED TO BE |
| | BATTERY POWERED. |
| | |
| | 31.3.5 EXTINGUISHMENT REQUIREMENTS. |
| | 31.3.5.1 RESERVED. |
| | 31.3.5.2* WHERE AN AUTOMATIC SPRINKLER SYSTEM IS |
| | INSTALLED, EITHER FOR |
| | TOTAL OR PARTIAL BUILDING COVERAGE, THE SYSTEM SHALL BE |
| | INSTALLED IN |
| | ACCORDANCE WITH SECTION 9.7, AS MODIFIED BY 31.3.5.3 |
| | AND 31.3.5.4. IN |
| | BUILDINGS FOUR OR FEWER STORIES ABOVE GRADE PLANE, |
| | SYSTEMS IN |
| | ACCORDANCE WITH NFPA 13R, STANDARD FOR THE INSTALLATION |
| | OF SPRINKLER |
| | SYSTEMS IN LOW-RISE RESIDENTIAL OCCUPANCIES, SHALL BE |
| | PERMITTED. |
| | |
| | ANY WORK ON THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS |
| | SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | ALL LIFE SAFETY SYSTEMS SHALL BE MAINTAINED THROUGHOUT |
| | DEMO AND RECONSTRUCTION. |
| | |
| | PLEASE PROVIDE DETAILS AND AN APPLICABLE NOTE OF |
| | ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 4) THERE ARE NO INDICATIONS OF ANY FIRE ALARM NOR SMOKE |
| | DETECTION/ALARMS IN THE AFFECTED UNITS. |
| | |
| | PLEASE PROVIDE DETAILS IN COMPLIANCE WITH NFPA 101. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |