2020-02-11 09:33:512017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20010107
 ADD: 315 ALMERIA RD. / 73 DWELLING UNITS
 CONT: TBD/ TO BE DETERMINED
 TEL: ???????
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 11/2020
 ACTION: DENIED
  
 1) THE COVERSHEET LIST UNDER THE HEADING APPLICABLE
 CODES INCLUDING THE EXISTING BUILDING CODE AND
 ACCESSIBILITY CODE.
  
 1A) WHAT THE DESIGNER OF RECORD DOES NOT PROVIDE IS THE
 OCCUPANCY GROUP, MINIMUM BUILDING TYPE, BUILDING
 HEIGHT, AREA PER STORY AND IS THE BUILDING FIRE
 SPRINKLERED. THESE ARE UNKNOWNS AND CRITICAL TO BE ABLE
 TO COMPLETE A BUILDING PLAN REVIEW FOR A COMMERCIAL
 BUILDING.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE
 107.3.5.1 COMMERCIAL BUILDINGS:
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLES 504.3, 504.4 & 506.2).
 IS THE BUILDING FIRE SPRINKLERED OR NOT, IS IT REQUIRED
 UNDER TODAY?S CODE?
  
 1B) THE DESIGNER OF RECORD HAS NOT SHOWN HOW COMPLIANCE
 WITH THE EXISTING BUILDING CODE SECTION 301.1 WILL BE
 ACHIEVED. ALL EXISTING BUILDINGS SHALL COMPLY WITH ONE
 OF THE METHODS LISTED IN SECTIONS 301.1.1 THROUGH
 301.1.3.
  
 1C) THE DESIGNER OF RECORD LIST ON THE COVERSHEET
 ACCESSIBLE DATA, 73 UNITS X .05= 4 ACCESSIBLE UNITS AND
 73 UNITS X .02= 2 HEAR/VISION UNITS. FROM THE
 INFORMATION PROVIDED FROM THE DESIGNER OF RECORD A
 THOROUGH REVIEW CANNOT BE DETERMINED. WHEN THE DESIGNER
 OF RECORD SHOWS ACCESSIBILITY REQUIREMENTS TO THE
 APARTMENT AS UPGRADES IN ACCESSIBILITY, THE QUESTION IS
 ASKED IS A PORTION OF THE APARTMENTS TO BE CONSIDERED
 TRANSIENT APARTMENTS WHERE IN THE BUILDING MORE THAN 25
 PER CENT OR MORE OF THE UNITS ARE ADVERTISED OR HELD
 OUT TO THE PUBLIC AS AVAILABLE FOR TRANSIENT USE (STAYS
 LESS THAN 30 DAYS)? FLORIDA STATUTE 509 WOULD KICK IN
 AND TOUGHS UNITS WHICH ARE PUBLIC LODGING, (TRANSIENT
 LODGING) WOULD NEED TO SHOW COMPLIANCE WITH THE 2017
 FLORIDA ACCESSIBILITY CODE AND FLORIDA STATUTE 509.
 LONG TERM STAYS OVER 30 DAYS IS NOT COVERED UNDER
 FLORIDA ACCESSIBILITY AND THIS BUILDING WAS BUILT AND
 OCCUPIED BEFORE FAIR HOUSING WOULD HAVE BEEN A SAFE
 HAVEN. IS THERE FEDERAL ASSISTANCE PROVIDED?
  
 1D) IF THIS BUILDING IS TO BE CONSIDERED TRANSIENT
 LODGING (OVER 25% OF THE UNITS TRANSIENT) PLEASE REVIEW
 IN THE 2017 FLORIDA ACCESSIBILITY CODE SECTION 224 .6.2
 FACILITIES WITH RESIDENTIAL UNITS AND TRANSIENT LODGING
 UNITS. RESIDENTIAL DWELLING UNITS THAT ARE DESIGNED AND
 CONSTRUCTED FOR RESIDENTIAL USE EXCLUSIVELY ARE NOT
 SUBJECT TO THE TRANSIENT LODGING STANDARDS. ONLY 2
 UNITS ARE FOR HEARING/ VISION IMPAIRED WHEREAS THE
 ACCESSIBILITY CODE TABLE 224.4 FOR 73 UNITS REQUIRES 7
 UNITS TO SHOW COMPLIANCE?
  
 1E) PLEASE PROVIDE A LIFE SAFETY PLAN ON HOW WORK WILL
 BE COMPLETED IN THE UNITS, WILL THERE STILL BE
 OCCUPANTS IN THE UNITS UNDER REMODELING, WILL THERE BE
 OCCUPANTS IN THERE UNITS ON THE SAME FLOOR AS OTHER
 UNITS ARE BEING REMODELED? PLEASE SHOW COMPLIANCE WITH
 THE 2017 FBC-B:
 1E)(1) 3302.1 ALTERATIONS AND REPAIRS. REQUIRED EXITS,
 EXISTING STRUCTURAL ELEMENTS, FIRE PROTECTION DEVICES
 AND SANITARY SAFEGUARDS SHALL BE MAINTAINED AT ALL
 TIMES DURING CONSTRUCTION, ALTERATIONS AND OR REPAIRS
 TO ANY BUILDING OR STRUCTURE.
 1E)(2) 3302.2 MANNER OF REMOVAL. WASTE MATERIALS SHALL
 BE REMOVED IN A MANNER THAT PREVENTS INJURY OR DAMAGE
 TO PERSONS, ADJOINING PROPERTIES AND THE PUBLIC-RIGHT
 OF WAYS.
 1E)(3) 3302.3 FIRE SAFETY DURING CONSTRUCTION. FIRE
 SAFETY DURING CONSTRUCTION SHALL COMPLY WITH THE
 APPLICABLE REQUIREMENTS OF THIS CODE AND THE PROVISIONS
 OF THE FLORIDA FIRE PREVENTION CODE.
  
 1F) THE ELEVATION VIEWS ON SHEET A-301 SHOWS THIS AS A
 4 STORY BUILDING BUT THE PLANS ONLY SHOW WORK ON FLOOR
 LEVELS 1-3, IS THERE NO WORK TO OCCUR ON THE 4TH FLOOR?
 IS THE 4TH FLOOR OCCUPIED? 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 1G) 2017 FBC- EXISTING BUILDING. 804.2.2 R-2 OCCUPANCY
 REQUIRES AUTOMATIC FIRE SPRINKLERS WHEN THE SHARED
 CORRIDORS AND EXITS HAVE AN OCCUPANT LOAD GREATER THAN
 30 OCCUPANTS.
  
 1H) 2017 FBC-EXISTING BUILDING CODE 804.4.1.6. A FIRE
 ALARM SYSTEM SHALL BE INSTALLED IN WORK AREAS OF R-2
 APARTMENT BUILDINGS AS REQUIRED BY THE FLORIDA FIRE
 PREVENTION CODE FOR EXISTING GROUP R-2 OCCUPANCIES.
  
 1I) THE PLANS DO NOT INDICATE IF THERE IS FIRE
 SEPARATION BETWEEN THE DWELLING UNITS AS WELL AS A FIRE
 RATED CORRIDOR. PLEASE REVIEW THE REQUIREMENTS OF THE
 2017 FBC-EXISTING BUILDING SECTION 803.6 FIRE
 RESISTANCE RATINGS AND IN THE FBC-B SECTION 420.2
 REQUIRED SEPARATION WALLS.
  
 1J) SHEET A-202 THE PROPOSED 1ST FLOOR PLAN CENTER OF
 BUILDING FRONT EXIT STAIRWAY SHOWS THE EXIT STAIRWAY
 DOOR WITH A IN-SWING DOOR. THE 2017 FBC-EXISTING
 BUILDING CODE SECTION 805.4.2 SHOW A INSWING DOOR,
 PLEASE SHOW COMPLIANCE WITH SECTION 805.4.2 AND OR
 PROVIDE THE OCCUPANT LOAD FOR THE 2ND FLOOR AND 3RD
 FLOOR SEPARATELY, NOT COMBINED.
  
 2) THE PROPOSED NEW ACCESSIBLE PARKING IS SHOWN ON
 SHEET A-002 AND DETAIL FOR STALL STANDARDS ON A-003.
 PLEASE UPDATE THE STALL AND ACCESS AISLES TO THE 2017
 ACCESSIBILITY REQUIREMENTS. AN ACCESSIBLE PARKING SPACE
 AND ACCESS AISLE, PLEASE SEE THE 2017 FBC-ACCESSIBILITY
 CODE 502.3.3 MARKING. ACCESS AISLES SHALL BE MARKED SO
 AS TO DISCOURAGE PARKING IN THEM. THE ACCESS AISLE MUST
 BE STRIPED DIAGONALLY TO DESIGNATE IT AS A NO-PARKING
 ZONE.
 ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF
 MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY
 BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 BECAUSE THESE REQUIREMENTS PERMIT THE VAN ACCESS AISLE
 TO BE AS WIDE AS A PARKING SPACE, IT IS IMPORTANT THAT
 THE AISLE BE CLEARLY MARKED. FLORIDA LAW, S.553.5041
 (5)(C)1., REQUIRES DIAGONAL STRIPING OF ACCESS AISLES.
 THE CITY OF W. P. B. MUNI CODE ARTICLE XV 94-485
 PARKING PROVIDES A DOUBLE LINED DIMENSIONED PARKING
 STALL DETAIL.
  
 3) SHEETS A-202 THE 1ST FLOOR LEVEL, SHEET A-203 THE
 2ND FLOOR LEVEL AND A-204 THE 3RD FLOOR LEVEL ALL SHOW
 THE PROPOSED WORK ON EACH OF THE FLOORS. WHAT ALL OF
 THESE FLOORS SHOW IS NEW A/C SPLIT SYSTEMS BEING
 INSTALLED IN EACH OF THESE UNITS. PLEASE PROVIDE HOW
 COMPLIANCE WILL BE ACHIEVED WITH THE 2017 ENERGY CODE
 SECTIONS:
 R101.5.1.2 COMMERCIAL AND RESIDENTIAL> 3 STORIES. SEE
 FBC- ENERGY CONSERVATION COMMERCIAL PROVISIONS.
 C401.2 APPLICATION. COMMERCIAL BUILDINGS SHALL COMPLY
 WITH ONE OF THE FOLLOWING:
 1) REQUIREMENTS OF ANSI/ ASHRAE/ IESNA 90.1 EXCLUDING
 9.4.1.1(G) OF THE STANDARD.
 2) THE REQUIREMENTS OF SECTIONS C402 THROUGH C405 IN
 ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH
 SECTION C406 AND TENANT SPACES SHALL COMPLY WITH
 SECTION C406.1.1.
 3) THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404,
 C405.2, C405.3, C405.5, C405.6 AND C405.7. THE BUILDING
 ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85% OF THE
 STANDARD REFERENCE DESIGN BUILDING.
  
 4) SHEET A-302 SHOW THE EAST & WEST WALLS WITH NEW
 PROPOSED MECHANICAL CHASES TO HOUSE THE MECHANICAL
 REFRIGERANT LINES. THERE IS NO STRUCTURAL PLANS ON HOW
 THE MECHANICAL CHASE ON THE EXTERIOR SIDES OF THE
 BUILDING ARE TO BE BUILT, SECURED TO THE BUILDING, AND
 THE SEALING OF THE EXTERIOR WALL PENETRATION OF THE
 REFRIGERANT LINES, FIRE RATING FOR THROUGH
 PENETRATIONS. NOR DOES SHEET A-703 DEPICT CORRECTLY THE
 ROOF PENETRATION FOR THE REFRIGERANT LINES. THEY SHOULD
 BE A THROUGH THE WALL PARAPET PENETRATION, OR IF THEY
 PENETRATE THE ROOF AS SHOWN THEN THERE NEEDS MORE CUT
 SECTIONS OF HOW THE REFRIGERANT LINES LEAVE THE NEW
 EXTERIOR CHASE AND RUN THROUGH THE ATTIC SPACE AND THEN
 PENETRATE FROM THE ATTIC SPACE AND THROUGH THE ROOF.
 THERE IS NOT ENOUGH INFORMATION TO THOROUGHLY DO A
 REVIEW ON THIS SUBJECT!!!!!
 CHASES VERSES SHAFTS. FBC-B 707.3.1 SHAFT ENCLOSURES
 SHALL COMPLY WITH 713.4.
 707.7 PENETRATIONS OF FIRE BARRIERS SHALL COMPLY WITH
 SECTION 714.
 FIRE BLOCKING SHALL COMPLY WITH 2017 FBC-B SECTION
 718.2.
 718.2.2 CONCEALED WALL SPACES.
  
 5) SHEET A-703 THE SPLIT SYSTEM SHOWS THE USER OF WOOD
 SLEEPERS TO MOUNT THE NEW A/C CONDENSING UNITS WITH
 LESS THAN 6 INCHES FROM THE ROOF FINISH TO THE
 UNDERSIDE OF THE NEW CONDENSING INSTALLATION. PLEASE
 NOTE IN THE 2017 FBC-B THE EXCEPTION TO USING SLEEPERS
 ON THE ROOF DECK IS IN EXISTING CONDITIONS, NOT NEW
 INSTALLATIONS. THE 2017 FBC-B REQUIRES MECHANICAL UNITS
 TO BE RAISED UP OFF THE ROOF TOP FOR THE APPLICATION OF
 RE-ROOFING, THERE IS ENOUGH CLEARANCE UNDER THE UNITS
 THAT THE A/C COMPRESSORS DO NOT NEED TO BE DETACHED AND
 RE-INSTALLED FOR RE-ROOFING. PLEASE REVIEW TABLE
 1510.10 FOR THE REQUIRED MINIMUM CLEARANCE BENEATH THE
 A/C STAND. THIS IS THE LOWEST HORIZONTAL FRAMING MEMBER
 OF THE STAND.
  
 6) SINCE THE A/C STANDS ARE TO BE INSTALLED ON THE 3RD
 FLOOR ROOF PLEAS PROVIDE THE WIND DESIGN CRITERIA.
  
 2017 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 7A) 2017 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(G) PRE-ENGINEERED A/C STANDS.
  
 7B) THE ROOF TOP A/C STAND PRODUCT APPROVALS WILL NEED
 TO BE REVIEWED BY THE DESIGNER OF RECORD. PLEASE
 IDENTIFY THE FOLLOWING REQUIREMENTS CALCULATING THE
 AREA (SIDE VIEW) OF THE ROOF TOP COMPRESSORS,
 CONFIGURATION ON STAND, THE MEAN ROOF HEIGHT OF THE
 STAND AND COMPRESSORS, WEIGHT, CIRCLED THE DESIGN
 PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT VERSES
 MOMENT FOR THE UNIT TO THE STAND AND THE STAND TO THE
 ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY THE
 DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO THE
 BUILDING DEPARTMENT.
  
 7C) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 7D) THE ROOF PLAN A-601 SHOWS THE PROPOSED A/C
 COMPRESSORS ON THE ROOF BUT NO WAY TO SERVICE THE
 UNITS. 2017 FBC-M 306.5. EQUIPMENT AND APPLIANCES ON
 ROOFS OR ELEVATED STRUCTURES. WHERE EQUIPMENT REQUIRING
 ACCESS OR APPLIANCES ARE LOCATED ON AN ELEVATED
 STRUCTURE OR ROOF OF A BUILDING SUCH AS PERSONNEL WILL
 HAVE TO CLIMB HIGHER THAN 16 FEET ABOVE GRADE TO ACCESS
 SUCH EQUIPMENT OR APPLIANCES, AN INTERIOR OR EXTERIOR
 MEANS OF EGRESS SHALL BE PROVIDED.
  
 7E) WHEN VIEWING THE ROOF TOP THROUGH GOGGLE MAPS IT
 APPEARS THE PARAPETS AROUND THE PERIMETER AND
 COURTYARDS MAY NEED GUARDS WHERE THE A/C CONDENSERS ARE
 WITHIN 10 FEET OF THE EDGE OF THE BUILDING.
 SHOW COMPLIANCE WITH FBC-B 1013.7 ROOF GUARDS/ ACCESS.
 GUARDS SHALL BE PROVIDED WHERE THE ROOF HATCH OPENING
 IS LOCATED WITHIN 10 FEET OF A ROOF EDGE OR OPEN SIDE
 OF A WALKING SURFACE AND SUCH EDGE OR OPEN SIDE IS
 LOCATED MORE THAN 30 INCHES ABOVE THE FLOOR, ROOF OR
 GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO
 PREVENT THE PASSAGE OF A SPHERE 21 INCHES (533 MM) IN
 DIAMETER.
  
 7F) ZONING MAY REQUIRE THE NEW A/C CONDENSERS TO BE
 SCREENED FROM VIEW. IF SO SHOW COMPLIANCE WITH THE 2017
 FBC-B SECTIONS:
 1509.6 MECHANICAL EQUIPMENT SCREENS. MECHANICAL
 EQUIPMENT SCREENS SHALL BE CONSTRUCTED OF THE MATERIALS
 SPECIFIED FOR THE EXTERIOR WALLS IN ACCORDANCE WITH THE
 TYPE OF CONSTRUCTION OF THE BUILDING. WHERE THE FIRE
 SEPARATION DISTANCE IS GREATER THAN 5 FEET (1524 MM),
 MECHANICAL EQUIPMENT SCREENS SHALL NOT BE REQUIRED TO
 COMPLY WITH THE FIRE-RESISTANCE RATING REQUIREMENTS.
 1509.6.1 HEIGHT LIMITATIONS. MECHANICAL EQUIPMENT
 SCREENS SHALL NOT EXCEED 18 FEET (5486 MM) IN HEIGHT
 ABOVE THE ROOF DECK, AS MEASURED TO THE HIGHEST POINT
 ON THE MECHANICAL EQUIPMENT SCREEN.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER