| 2020-02-11 09:33:51 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20010107 |
| | ADD: 315 ALMERIA RD. / 73 DWELLING UNITS |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: ??????? |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. FEB. 11/2020 |
| | ACTION: DENIED |
| | |
| | 1) THE COVERSHEET LIST UNDER THE HEADING APPLICABLE |
| | CODES INCLUDING THE EXISTING BUILDING CODE AND |
| | ACCESSIBILITY CODE. |
| | |
| | 1A) WHAT THE DESIGNER OF RECORD DOES NOT PROVIDE IS THE |
| | OCCUPANCY GROUP, MINIMUM BUILDING TYPE, BUILDING |
| | HEIGHT, AREA PER STORY AND IS THE BUILDING FIRE |
| | SPRINKLERED. THESE ARE UNKNOWNS AND CRITICAL TO BE ABLE |
| | TO COMPLETE A BUILDING PLAN REVIEW FOR A COMMERCIAL |
| | BUILDING. |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATIVE CODE |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED |
| | MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE |
| | TABLES 504.3, 504.4 & 506.2). |
| | IS THE BUILDING FIRE SPRINKLERED OR NOT, IS IT REQUIRED |
| | UNDER TODAY?S CODE? |
| | |
| | 1B) THE DESIGNER OF RECORD HAS NOT SHOWN HOW COMPLIANCE |
| | WITH THE EXISTING BUILDING CODE SECTION 301.1 WILL BE |
| | ACHIEVED. ALL EXISTING BUILDINGS SHALL COMPLY WITH ONE |
| | OF THE METHODS LISTED IN SECTIONS 301.1.1 THROUGH |
| | 301.1.3. |
| | |
| | 1C) THE DESIGNER OF RECORD LIST ON THE COVERSHEET |
| | ACCESSIBLE DATA, 73 UNITS X .05= 4 ACCESSIBLE UNITS AND |
| | 73 UNITS X .02= 2 HEAR/VISION UNITS. FROM THE |
| | INFORMATION PROVIDED FROM THE DESIGNER OF RECORD A |
| | THOROUGH REVIEW CANNOT BE DETERMINED. WHEN THE DESIGNER |
| | OF RECORD SHOWS ACCESSIBILITY REQUIREMENTS TO THE |
| | APARTMENT AS UPGRADES IN ACCESSIBILITY, THE QUESTION IS |
| | ASKED IS A PORTION OF THE APARTMENTS TO BE CONSIDERED |
| | TRANSIENT APARTMENTS WHERE IN THE BUILDING MORE THAN 25 |
| | PER CENT OR MORE OF THE UNITS ARE ADVERTISED OR HELD |
| | OUT TO THE PUBLIC AS AVAILABLE FOR TRANSIENT USE (STAYS |
| | LESS THAN 30 DAYS)? FLORIDA STATUTE 509 WOULD KICK IN |
| | AND TOUGHS UNITS WHICH ARE PUBLIC LODGING, (TRANSIENT |
| | LODGING) WOULD NEED TO SHOW COMPLIANCE WITH THE 2017 |
| | FLORIDA ACCESSIBILITY CODE AND FLORIDA STATUTE 509. |
| | LONG TERM STAYS OVER 30 DAYS IS NOT COVERED UNDER |
| | FLORIDA ACCESSIBILITY AND THIS BUILDING WAS BUILT AND |
| | OCCUPIED BEFORE FAIR HOUSING WOULD HAVE BEEN A SAFE |
| | HAVEN. IS THERE FEDERAL ASSISTANCE PROVIDED? |
| | |
| | 1D) IF THIS BUILDING IS TO BE CONSIDERED TRANSIENT |
| | LODGING (OVER 25% OF THE UNITS TRANSIENT) PLEASE REVIEW |
| | IN THE 2017 FLORIDA ACCESSIBILITY CODE SECTION 224 .6.2 |
| | FACILITIES WITH RESIDENTIAL UNITS AND TRANSIENT LODGING |
| | UNITS. RESIDENTIAL DWELLING UNITS THAT ARE DESIGNED AND |
| | CONSTRUCTED FOR RESIDENTIAL USE EXCLUSIVELY ARE NOT |
| | SUBJECT TO THE TRANSIENT LODGING STANDARDS. ONLY 2 |
| | UNITS ARE FOR HEARING/ VISION IMPAIRED WHEREAS THE |
| | ACCESSIBILITY CODE TABLE 224.4 FOR 73 UNITS REQUIRES 7 |
| | UNITS TO SHOW COMPLIANCE? |
| | |
| | 1E) PLEASE PROVIDE A LIFE SAFETY PLAN ON HOW WORK WILL |
| | BE COMPLETED IN THE UNITS, WILL THERE STILL BE |
| | OCCUPANTS IN THE UNITS UNDER REMODELING, WILL THERE BE |
| | OCCUPANTS IN THERE UNITS ON THE SAME FLOOR AS OTHER |
| | UNITS ARE BEING REMODELED? PLEASE SHOW COMPLIANCE WITH |
| | THE 2017 FBC-B: |
| | 1E)(1) 3302.1 ALTERATIONS AND REPAIRS. REQUIRED EXITS, |
| | EXISTING STRUCTURAL ELEMENTS, FIRE PROTECTION DEVICES |
| | AND SANITARY SAFEGUARDS SHALL BE MAINTAINED AT ALL |
| | TIMES DURING CONSTRUCTION, ALTERATIONS AND OR REPAIRS |
| | TO ANY BUILDING OR STRUCTURE. |
| | 1E)(2) 3302.2 MANNER OF REMOVAL. WASTE MATERIALS SHALL |
| | BE REMOVED IN A MANNER THAT PREVENTS INJURY OR DAMAGE |
| | TO PERSONS, ADJOINING PROPERTIES AND THE PUBLIC-RIGHT |
| | OF WAYS. |
| | 1E)(3) 3302.3 FIRE SAFETY DURING CONSTRUCTION. FIRE |
| | SAFETY DURING CONSTRUCTION SHALL COMPLY WITH THE |
| | APPLICABLE REQUIREMENTS OF THIS CODE AND THE PROVISIONS |
| | OF THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | 1F) THE ELEVATION VIEWS ON SHEET A-301 SHOWS THIS AS A |
| | 4 STORY BUILDING BUT THE PLANS ONLY SHOW WORK ON FLOOR |
| | LEVELS 1-3, IS THERE NO WORK TO OCCUR ON THE 4TH FLOOR? |
| | IS THE 4TH FLOOR OCCUPIED? 107.2.1.2 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 1G) 2017 FBC- EXISTING BUILDING. 804.2.2 R-2 OCCUPANCY |
| | REQUIRES AUTOMATIC FIRE SPRINKLERS WHEN THE SHARED |
| | CORRIDORS AND EXITS HAVE AN OCCUPANT LOAD GREATER THAN |
| | 30 OCCUPANTS. |
| | |
| | 1H) 2017 FBC-EXISTING BUILDING CODE 804.4.1.6. A FIRE |
| | ALARM SYSTEM SHALL BE INSTALLED IN WORK AREAS OF R-2 |
| | APARTMENT BUILDINGS AS REQUIRED BY THE FLORIDA FIRE |
| | PREVENTION CODE FOR EXISTING GROUP R-2 OCCUPANCIES. |
| | |
| | 1I) THE PLANS DO NOT INDICATE IF THERE IS FIRE |
| | SEPARATION BETWEEN THE DWELLING UNITS AS WELL AS A FIRE |
| | RATED CORRIDOR. PLEASE REVIEW THE REQUIREMENTS OF THE |
| | 2017 FBC-EXISTING BUILDING SECTION 803.6 FIRE |
| | RESISTANCE RATINGS AND IN THE FBC-B SECTION 420.2 |
| | REQUIRED SEPARATION WALLS. |
| | |
| | 1J) SHEET A-202 THE PROPOSED 1ST FLOOR PLAN CENTER OF |
| | BUILDING FRONT EXIT STAIRWAY SHOWS THE EXIT STAIRWAY |
| | DOOR WITH A IN-SWING DOOR. THE 2017 FBC-EXISTING |
| | BUILDING CODE SECTION 805.4.2 SHOW A INSWING DOOR, |
| | PLEASE SHOW COMPLIANCE WITH SECTION 805.4.2 AND OR |
| | PROVIDE THE OCCUPANT LOAD FOR THE 2ND FLOOR AND 3RD |
| | FLOOR SEPARATELY, NOT COMBINED. |
| | |
| | 2) THE PROPOSED NEW ACCESSIBLE PARKING IS SHOWN ON |
| | SHEET A-002 AND DETAIL FOR STALL STANDARDS ON A-003. |
| | PLEASE UPDATE THE STALL AND ACCESS AISLES TO THE 2017 |
| | ACCESSIBILITY REQUIREMENTS. AN ACCESSIBLE PARKING SPACE |
| | AND ACCESS AISLE, PLEASE SEE THE 2017 FBC-ACCESSIBILITY |
| | CODE 502.3.3 MARKING. ACCESS AISLES SHALL BE MARKED SO |
| | AS TO DISCOURAGE PARKING IN THEM. THE ACCESS AISLE MUST |
| | BE STRIPED DIAGONALLY TO DESIGNATE IT AS A NO-PARKING |
| | ZONE. |
| | ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF |
| | MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY |
| | BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS. |
| | BECAUSE THESE REQUIREMENTS PERMIT THE VAN ACCESS AISLE |
| | TO BE AS WIDE AS A PARKING SPACE, IT IS IMPORTANT THAT |
| | THE AISLE BE CLEARLY MARKED. FLORIDA LAW, S.553.5041 |
| | (5)(C)1., REQUIRES DIAGONAL STRIPING OF ACCESS AISLES. |
| | THE CITY OF W. P. B. MUNI CODE ARTICLE XV 94-485 |
| | PARKING PROVIDES A DOUBLE LINED DIMENSIONED PARKING |
| | STALL DETAIL. |
| | |
| | 3) SHEETS A-202 THE 1ST FLOOR LEVEL, SHEET A-203 THE |
| | 2ND FLOOR LEVEL AND A-204 THE 3RD FLOOR LEVEL ALL SHOW |
| | THE PROPOSED WORK ON EACH OF THE FLOORS. WHAT ALL OF |
| | THESE FLOORS SHOW IS NEW A/C SPLIT SYSTEMS BEING |
| | INSTALLED IN EACH OF THESE UNITS. PLEASE PROVIDE HOW |
| | COMPLIANCE WILL BE ACHIEVED WITH THE 2017 ENERGY CODE |
| | SECTIONS: |
| | R101.5.1.2 COMMERCIAL AND RESIDENTIAL> 3 STORIES. SEE |
| | FBC- ENERGY CONSERVATION COMMERCIAL PROVISIONS. |
| | C401.2 APPLICATION. COMMERCIAL BUILDINGS SHALL COMPLY |
| | WITH ONE OF THE FOLLOWING: |
| | 1) REQUIREMENTS OF ANSI/ ASHRAE/ IESNA 90.1 EXCLUDING |
| | 9.4.1.1(G) OF THE STANDARD. |
| | 2) THE REQUIREMENTS OF SECTIONS C402 THROUGH C405 IN |
| | ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH |
| | SECTION C406 AND TENANT SPACES SHALL COMPLY WITH |
| | SECTION C406.1.1. |
| | 3) THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404, |
| | C405.2, C405.3, C405.5, C405.6 AND C405.7. THE BUILDING |
| | ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85% OF THE |
| | STANDARD REFERENCE DESIGN BUILDING. |
| | |
| | 4) SHEET A-302 SHOW THE EAST & WEST WALLS WITH NEW |
| | PROPOSED MECHANICAL CHASES TO HOUSE THE MECHANICAL |
| | REFRIGERANT LINES. THERE IS NO STRUCTURAL PLANS ON HOW |
| | THE MECHANICAL CHASE ON THE EXTERIOR SIDES OF THE |
| | BUILDING ARE TO BE BUILT, SECURED TO THE BUILDING, AND |
| | THE SEALING OF THE EXTERIOR WALL PENETRATION OF THE |
| | REFRIGERANT LINES, FIRE RATING FOR THROUGH |
| | PENETRATIONS. NOR DOES SHEET A-703 DEPICT CORRECTLY THE |
| | ROOF PENETRATION FOR THE REFRIGERANT LINES. THEY SHOULD |
| | BE A THROUGH THE WALL PARAPET PENETRATION, OR IF THEY |
| | PENETRATE THE ROOF AS SHOWN THEN THERE NEEDS MORE CUT |
| | SECTIONS OF HOW THE REFRIGERANT LINES LEAVE THE NEW |
| | EXTERIOR CHASE AND RUN THROUGH THE ATTIC SPACE AND THEN |
| | PENETRATE FROM THE ATTIC SPACE AND THROUGH THE ROOF. |
| | THERE IS NOT ENOUGH INFORMATION TO THOROUGHLY DO A |
| | REVIEW ON THIS SUBJECT!!!!! |
| | CHASES VERSES SHAFTS. FBC-B 707.3.1 SHAFT ENCLOSURES |
| | SHALL COMPLY WITH 713.4. |
| | 707.7 PENETRATIONS OF FIRE BARRIERS SHALL COMPLY WITH |
| | SECTION 714. |
| | FIRE BLOCKING SHALL COMPLY WITH 2017 FBC-B SECTION |
| | 718.2. |
| | 718.2.2 CONCEALED WALL SPACES. |
| | |
| | 5) SHEET A-703 THE SPLIT SYSTEM SHOWS THE USER OF WOOD |
| | SLEEPERS TO MOUNT THE NEW A/C CONDENSING UNITS WITH |
| | LESS THAN 6 INCHES FROM THE ROOF FINISH TO THE |
| | UNDERSIDE OF THE NEW CONDENSING INSTALLATION. PLEASE |
| | NOTE IN THE 2017 FBC-B THE EXCEPTION TO USING SLEEPERS |
| | ON THE ROOF DECK IS IN EXISTING CONDITIONS, NOT NEW |
| | INSTALLATIONS. THE 2017 FBC-B REQUIRES MECHANICAL UNITS |
| | TO BE RAISED UP OFF THE ROOF TOP FOR THE APPLICATION OF |
| | RE-ROOFING, THERE IS ENOUGH CLEARANCE UNDER THE UNITS |
| | THAT THE A/C COMPRESSORS DO NOT NEED TO BE DETACHED AND |
| | RE-INSTALLED FOR RE-ROOFING. PLEASE REVIEW TABLE |
| | 1510.10 FOR THE REQUIRED MINIMUM CLEARANCE BENEATH THE |
| | A/C STAND. THIS IS THE LOWEST HORIZONTAL FRAMING MEMBER |
| | OF THE STAND. |
| | |
| | 6) SINCE THE A/C STANDS ARE TO BE INSTALLED ON THE 3RD |
| | FLOOR ROOF PLEAS PROVIDE THE WIND DESIGN CRITERIA. |
| | |
| | 2017 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING |
| | INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN, |
| | REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF |
| | THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE: |
| | 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| | 2. RISK CATEGORY. |
| | 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. |
| | 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| | 6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 7A) 2017 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE |
| | CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(G) PRE-ENGINEERED A/C STANDS. |
| | |
| | 7B) THE ROOF TOP A/C STAND PRODUCT APPROVALS WILL NEED |
| | TO BE REVIEWED BY THE DESIGNER OF RECORD. PLEASE |
| | IDENTIFY THE FOLLOWING REQUIREMENTS CALCULATING THE |
| | AREA (SIDE VIEW) OF THE ROOF TOP COMPRESSORS, |
| | CONFIGURATION ON STAND, THE MEAN ROOF HEIGHT OF THE |
| | STAND AND COMPRESSORS, WEIGHT, CIRCLED THE DESIGN |
| | PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT VERSES |
| | MOMENT FOR THE UNIT TO THE STAND AND THE STAND TO THE |
| | ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY THE |
| | DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO THE |
| | BUILDING DEPARTMENT. |
| | |
| | 7C) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 7D) THE ROOF PLAN A-601 SHOWS THE PROPOSED A/C |
| | COMPRESSORS ON THE ROOF BUT NO WAY TO SERVICE THE |
| | UNITS. 2017 FBC-M 306.5. EQUIPMENT AND APPLIANCES ON |
| | ROOFS OR ELEVATED STRUCTURES. WHERE EQUIPMENT REQUIRING |
| | ACCESS OR APPLIANCES ARE LOCATED ON AN ELEVATED |
| | STRUCTURE OR ROOF OF A BUILDING SUCH AS PERSONNEL WILL |
| | HAVE TO CLIMB HIGHER THAN 16 FEET ABOVE GRADE TO ACCESS |
| | SUCH EQUIPMENT OR APPLIANCES, AN INTERIOR OR EXTERIOR |
| | MEANS OF EGRESS SHALL BE PROVIDED. |
| | |
| | 7E) WHEN VIEWING THE ROOF TOP THROUGH GOGGLE MAPS IT |
| | APPEARS THE PARAPETS AROUND THE PERIMETER AND |
| | COURTYARDS MAY NEED GUARDS WHERE THE A/C CONDENSERS ARE |
| | WITHIN 10 FEET OF THE EDGE OF THE BUILDING. |
| | SHOW COMPLIANCE WITH FBC-B 1013.7 ROOF GUARDS/ ACCESS. |
| | GUARDS SHALL BE PROVIDED WHERE THE ROOF HATCH OPENING |
| | IS LOCATED WITHIN 10 FEET OF A ROOF EDGE OR OPEN SIDE |
| | OF A WALKING SURFACE AND SUCH EDGE OR OPEN SIDE IS |
| | LOCATED MORE THAN 30 INCHES ABOVE THE FLOOR, ROOF OR |
| | GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO |
| | PREVENT THE PASSAGE OF A SPHERE 21 INCHES (533 MM) IN |
| | DIAMETER. |
| | |
| | 7F) ZONING MAY REQUIRE THE NEW A/C CONDENSERS TO BE |
| | SCREENED FROM VIEW. IF SO SHOW COMPLIANCE WITH THE 2017 |
| | FBC-B SECTIONS: |
| | 1509.6 MECHANICAL EQUIPMENT SCREENS. MECHANICAL |
| | EQUIPMENT SCREENS SHALL BE CONSTRUCTED OF THE MATERIALS |
| | SPECIFIED FOR THE EXTERIOR WALLS IN ACCORDANCE WITH THE |
| | TYPE OF CONSTRUCTION OF THE BUILDING. WHERE THE FIRE |
| | SEPARATION DISTANCE IS GREATER THAN 5 FEET (1524 MM), |
| | MECHANICAL EQUIPMENT SCREENS SHALL NOT BE REQUIRED TO |
| | COMPLY WITH THE FIRE-RESISTANCE RATING REQUIREMENTS. |
| | 1509.6.1 HEIGHT LIMITATIONS. MECHANICAL EQUIPMENT |
| | SCREENS SHALL NOT EXCEED 18 FEET (5486 MM) IN HEIGHT |
| | ABOVE THE ROOF DECK, AS MEASURED TO THE HIGHEST POINT |
| | ON THE MECHANICAL EQUIPMENT SCREEN. |
| | |
| | 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |