| 2020-02-08 12:48:26 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. DESIGNS OVER $125,000 MUST BE DESIGNED AND |
| | SIGNED/SEALED BY A DESIGN PROFESSIONAL. F.S. |
| | 471.003(2)(H)(1) |
| | |
| | 2. PROVIDE UL OR OTHER NRTL (NATIONALLY RECOGNIZED |
| | TESTING LABORATORY) LISTINGS FOR ALL |
| | DEVICES/MATERIALS/AND EQUIPMENT. LIGHT FIXTURES, LIGHT |
| | POLES, ETC. NEC 90.7, 110.2, 110.3 FBC 107.2.1 |
| | |
| | 3. FBC-107.1 GENERAL - FAC 61G15-23.002 - PROVIDE A |
| | TITLE BLOCK FOR THE ENGINEER OF RECORD CONSISTENT WITH |
| | THE REQUIREMENTS OF THIS SECTION, E.G.: FIRM NAME, |
| | LICENSE NUMBER, PHONE NUMBER...ETC. |
| | |
| | 4. ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 405.1 |
| | SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT |
| | OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & |
| | TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME |
| | SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING |
| | DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. |
| | FBC-EC 405.2.5 (A NOTE ON PLAN WILL SUFFICE). |
| | |
| | 5.PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | |
| | 6.PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE |
| | MARKED WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT |
| | AVAILABLE PER NEC 110.24. LABELS OUTDOORS MUST BE |
| | SUFFICIENT TO WITHSTAND THE WEATHER AND ELEMENTS. |
| | |
| | 7.PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |