| 2020-01-22 16:49:26 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #20010067 |
| | 1/22/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) ACCORDING TO THE PALM BEACH COUNTY APPRAISER'S |
| | REPORT AND WEST PALM BEACH PERMIT RECORDS, THE EXISTING |
| | AC SYSTEM WAS NEVER LEGALLY PERMITTED AND MUST NOW MEET |
| | COMPLIANCE AS A NEW SYSTEM BEING INSTALLED IN A |
| | PREVIOUSLY UNCONDITIONED BUILDING. PLEASE PROVIDE THE |
| | FOLLOWING: |
| | |
| | A) ENERGY COMPLIANCE REPORT- SECTION R503.2 FBC EC. |
| | |
| | B) AC COOLING AND HEATING CALCULATIONS- SECTION |
| | R403.6.1 FBC EC. |
| | |
| | 2) PROVIDE AN AC EQUIPMENT SCHEDULE ON THE PLAN THAT |
| | INCLUDES THE MAKE AND MODEL NUMBERS OF THE CONDENSER |
| | AND THE AIR HANDLER, COOLING AND HEATING CAPACITIES, |
| | TOTAL AIRFLOW CFMS, AND EFFICIENCY RATING- TABLE |
| | C403.2.3(1) FBC EC. |
| | |
| | 3) EXHAUST VENTILATION FOR THE KITCHEN AT A RATE OF 100 |
| | CFMS INTERMITTENT OR 25 CFMS CONTINUOUS IS REQUIRED PER |
| | TABLE M1507.4 FBC RES. INDICATE IF A RANGE HOOD WILL BE |
| | INSTALLED OR HOW COMPLIANCE WILL BE MET- SEE M1503 FBC |
| | RES. |
| | |
| | 4) INDICATE HOW THE NEW BATHROOM WILL BE VENTILATED- |
| | REFER TO SECTION R303.3 AND M1507 FBC RES. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |
| | |
| | |