Plan Review Notes
Plan Review Notes For Permit 20010046
Permit Number 20010046
Review Stop B
Sequence Number 1
Notes
Date Text
2020-02-11 13:09:162017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20010046
 ADD: 1880 PALM BEACH LAKES BLVD.
 CONT: TBD/ TO BE DETERMINED
 TEL: ???????
 E-MAIL: [email protected] CONTACT: ASHLEY ROSADO
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 11/2020
 ACTION: DENIED
  
 1) THE LIFE SAFETY SHEET LS1 DID NOT PROVIDE TO WHICH
 RACK STORAGE UNITS WERE TO BE EXTENDED, IT IS NOT CLEAR
 IF CERTAIN RACKS ARE TO BE EXTENDED, OR ALL RACKS ARE
 TO BE EXTENDED. 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2) THE COVERSHEET/ INDEX NOR THE LIFE SAFETY SHEET
 PROVIDE ANY HELP IN DETERMINING IF THERE IS TO BE
 ADDITIONAL FIRE SPRINKLER WORK TO BE COMPLETED SINCE
 SHEET F-4 FIXTURE EXTENSION PLAN SHOWS THE RACK STORAGE
 UNITS EXTENDING TO THE BOTTOM CHORD OF THE BAR JOIST.
 THE FLORIDA FIRE PREVENTION CODE ADDRESSES HIGH PILED
 STORAGE FOR IN MERCANTILE OCCUPANCIES. 2017 FBC-B
 SECTION 903.2.7.1.
  
 3) SHEET F-4 FIXTURE EXTENSION PLAN NOTE # 3 INDICATES
 ALL FIXTURE EXTENSIONS TO BE SUSPENDED FROM THE CEILING
 USING UNISTRUCT PER FIXTURE EXTENSION ATTACHMENT
 DETAILS OR INDICATED OTHERWISE BY THE STRUCTURAL
 ENGINEER. THIS STATEMENT STATES THE FIXTURE EXTENSION
 IS TO BE HUNG FROM THE CEILING. THE DETAIL ON THE
 FIXTURE PLAN SHOWS UNISTRUCT BEING HUNG FROM THE BOTTOM
 CHORD OF THE BAR JOIST. IS THE INTENT FOR THE FUTURE
 EXTENSION TO BE SUSPENDED FROM THE BAR JOIST? HAS A
 STRUCTURAL ENGINEER BEEN BROUGHT IN FOR THE ADDITIONAL
 LOADING TO THE BAR JOIST. IF THE EXTENSIONS ARE TRULY
 BEING HUNG FROM THE BAR JOIST WHAT ADDITIONAL LOADING
 DEAD LOADS AND LIVE LOADS ARE BEING ADDED? OR ARE THE
 FIXTURE EXTENSIONS TRANSFERRING THE LOADS DOWN THE LEGS
 TO THE FLOOR? AGAIN HAS THE ADDITIONAL LOADING ON THE
 RACK STORAGE UNITS DEAD & LIVE LOADS BEEN CALCULATED
 FOR THE RACK STORAGE UNITS? OR ARE THE VERTICAL FIXTURE
 EXTENSIONS USING THE UNISTRUCT BEING BOLTED TO THE BAR
 JOIST JUST FOR STABILIZING? 107. 2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  