Plan Review Notes
Plan Review Notes For Permit 20010044
Permit Number 20010044
Review Stop P
Sequence Number 1
Notes
Date Text
2020-01-10 09:03:191ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHTS. CL4-CL5 HAVE NOTES AT THE BOTTOM OF THE SHEETS
 DRAWINGS ARE FOR COMMUNICATION PURPOSES ONLY IS THIS A
 TYPE SHOULD READ FOR CONSTRUCTION PURPOSES ONLY PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1 ADDITIONAL
 INFORMATION REQUIRED.
  
 2. AN REDUCED PRESSURE PRINCIPLE ASSEMBLY OR RP IS
 REQUIRED AT THE METER. PER WPB UTILITIES DEPARTMENT AND
 WPB CROSS CONNECTION CONTROL MANUAL
  
 3. PLACE NOTE ON PLAN SEPARATE PERMIT REQUIRED FOR RP
 BACK FLOW DEVICE. PER WPB UTILITIES DEPARTMENT
  
 4. IRRIGATION/SPRINKLER SYSTEMS AND RISERS FOR SPRAY
 HEADS SHALL NOT BE INSTALLED WITHIN 1 FOOT OF THE
 BUILDING SIDEWALL. PER FBC PL 318.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]