| 2020-01-18 11:16:09 | PLAN REVIEW - BUILDING |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE FINISHED FLOOR ELEVATION. |
| | |
| | R403.1.7.3 FOUNDATION ELEVATION. |
| | ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION |
| | SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER |
| | AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED |
| | DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2 |
| | PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO |
| | THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN |
| | BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF |
| | DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT |
| | ALL LOCATIONS ON THE SITE. |
| | |
| | 2. BUILDER SHALL SIGN ENERGY SUBMITTAL. |
| | |
| | FLORIDA STATUTE 633.021, AND SECTION 107.2.1 WPB |
| | AMENDMENTS TO THE FBC. |
| | |
| | 3. ENERGY SUBMITTAL INDICATES ATTIC INSULATION SHALL BE |
| | BLOWN IN. PROVIDE PRODUCT APPROVAL OR ICC ES REPORT. |
| | |