| Plan Review Notes For Permit 19121112 |
| Permit Number |
19121112 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-07-13 15:30:38 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | ALL COMMENTS HAVE BEEN ADDRESSED EXCEPT THE FAULT | | | CURRENT CALCULATION. | | | | | | PANEL DETAIL SHOWS PANEL IS RATED AT 10K, NO | | | CALCULATION HAS BEEN PROVIDED SO I AM TO ASSUME THAT | | | THIS PANEOL WILL NEED TO BE RATED AT 22K. | | | | | | PLEASE SUBMIT THE AIC CALCULATION PER 110.9, 110.10, | | | ALSO PLACE NOTE FOR DECAL ON SERVICE PER 110.24 |
|