Plan Review Notes
Plan Review Notes For Permit 19121112
Permit Number 19121112
Review Stop E
Sequence Number 1
Notes
Date Text
2020-01-03 10:53:01FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VLAUE FOR THE WORK SHOWN IS TOO LOW, PLEASE SUBMIT A
 SIGNED CONTRACT WITH THE OWNER.
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) SHOWS TWO (2) CIRCUITS MAINS CANNOT BE SMALLER THEN
 30A. 230.79(B) (B) TWO-CIRCUIT INSTALLATIONS. FOR
 INSTALLATIONS CONSISTING OF NOT MORE THAN TWO 2-WIRE
 BRANCH CIRCUITS, THE SERVICE DISCONNECTING MEANS SHALL
 HAVE A RATING OF NOT LESS THAN 30 AMPERES.
  
 3) NEED THE AVAILABLE FAULT CURRENT RATING FOR THE
 SERVICE. 110.10 , 110.24 AVAILABLE FAULT CURRENT ( A)
 FIELD MARKING. SERVICE EQUIPMENT IN OTHER THAN DWELLING
 UNITS SHALL BE LEGIBLY MARKED IN THE FIELD WITH THE
 MAXIMUM AVAILABLE FAULT CURRENT. THE FIELD MARKING(S)
 SHALL INCLUDE THE DATE THE FAULT-CURRENT CALCULATION
 WAS PERFORMED AND BE OF SUFFICIENT DURABILITY TO
 WITHSTAND THE ENVIRONMENT INVOLVED.
  
 4) PANEL BOARD NEEDS TO BE LISTED 110.3, 230.66 MARKING
 SERVICE EQUIPMENT RATED AT 1000 VOLTS OR LESS SHALL BE
 MARKED TO IDENTIFY IT AS BEING SUITABLE FOR USE AS
 SERVICE EQUIPMENT. ALL SERVICE EQUIPMENT SHALL BE L
 ISTED. INDIVIDUAL METER SOCKET ENCLOSURES SHALL NOT BE
 CONSIDERED SERVICE EQUIPMENT.
  
 5) CUT SHEETS FOR SURGE ARRESTOR 110.3
  
 6) 250.94 BONDING FOR OTHER SYSTEMS AN INTERSYSTEM
 BONDING TERMINATION FOR CONNECTING INTERSYSTEM BONDING
 CONDUCTORS REQUIRED FOR OTHER SYSTEMS SHALL BE PROVIDED
 EXTERNAL TO ENCLOSURES AT THE SERVICE EQUIPMENT OR
 METERING EQUIPMENT ENCLOSURE AND AT THE DISCONNECTING
 MEANS FOR ANY ADDITIONAL BUILDINGS OR STRUCTURES.
  
  