| 2020-01-03 10:53:01 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | 1) VLAUE FOR THE WORK SHOWN IS TOO LOW, PLEASE SUBMIT A |
| | SIGNED CONTRACT WITH THE OWNER. |
| | |
| | 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF |
| | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF |
| | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE |
| | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, |
| | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS |
| | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE |
| | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION |
| | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT |
| | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, |
| | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, |
| | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | 2) SHOWS TWO (2) CIRCUITS MAINS CANNOT BE SMALLER THEN |
| | 30A. 230.79(B) (B) TWO-CIRCUIT INSTALLATIONS. FOR |
| | INSTALLATIONS CONSISTING OF NOT MORE THAN TWO 2-WIRE |
| | BRANCH CIRCUITS, THE SERVICE DISCONNECTING MEANS SHALL |
| | HAVE A RATING OF NOT LESS THAN 30 AMPERES. |
| | |
| | 3) NEED THE AVAILABLE FAULT CURRENT RATING FOR THE |
| | SERVICE. 110.10 , 110.24 AVAILABLE FAULT CURRENT ( A) |
| | FIELD MARKING. SERVICE EQUIPMENT IN OTHER THAN DWELLING |
| | UNITS SHALL BE LEGIBLY MARKED IN THE FIELD WITH THE |
| | MAXIMUM AVAILABLE FAULT CURRENT. THE FIELD MARKING(S) |
| | SHALL INCLUDE THE DATE THE FAULT-CURRENT CALCULATION |
| | WAS PERFORMED AND BE OF SUFFICIENT DURABILITY TO |
| | WITHSTAND THE ENVIRONMENT INVOLVED. |
| | |
| | 4) PANEL BOARD NEEDS TO BE LISTED 110.3, 230.66 MARKING |
| | SERVICE EQUIPMENT RATED AT 1000 VOLTS OR LESS SHALL BE |
| | MARKED TO IDENTIFY IT AS BEING SUITABLE FOR USE AS |
| | SERVICE EQUIPMENT. ALL SERVICE EQUIPMENT SHALL BE L |
| | ISTED. INDIVIDUAL METER SOCKET ENCLOSURES SHALL NOT BE |
| | CONSIDERED SERVICE EQUIPMENT. |
| | |
| | 5) CUT SHEETS FOR SURGE ARRESTOR 110.3 |
| | |
| | 6) 250.94 BONDING FOR OTHER SYSTEMS AN INTERSYSTEM |
| | BONDING TERMINATION FOR CONNECTING INTERSYSTEM BONDING |
| | CONDUCTORS REQUIRED FOR OTHER SYSTEMS SHALL BE PROVIDED |
| | EXTERNAL TO ENCLOSURES AT THE SERVICE EQUIPMENT OR |
| | METERING EQUIPMENT ENCLOSURE AND AT THE DISCONNECTING |
| | MEANS FOR ANY ADDITIONAL BUILDINGS OR STRUCTURES. |
| | |
| | |