2020-01-06 14:30:07FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NO ADDED VALUE FOR THE ADDITIONAL WORK ADDED TO THE
 SYSTEM.
  
 2) PAGE PV-3.1OW IS TAP MADE INTO THE SERVICE? LOOKS
 LIKE A LOAD SIDE TAP AND LOOKS TO BE MORE THAN 20%?
  
 3) PAGE PV-3.1 WHAT SIZE BATTERY IS BEING USED RISER
 SHOWS 5KW BUT CUT SHEETS SHOW 9.8KW ???
  
 4) BACKUP PANEL CUTSHEETS AND PANEL SCHEDULE.
  
 5) OCP FOR BATTERY WHERE IS IT AND WHAT SIZE IS IT,