| Plan Review Notes For Permit 19121066 |
| Permit Number |
19121066 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-01-06 14:30:07 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) NO ADDED VALUE FOR THE ADDITIONAL WORK ADDED TO THE | | | SYSTEM. | | | | | | 2) PAGE PV-3.1OW IS TAP MADE INTO THE SERVICE? LOOKS | | | LIKE A LOAD SIDE TAP AND LOOKS TO BE MORE THAN 20%? | | | | | | 3) PAGE PV-3.1 WHAT SIZE BATTERY IS BEING USED RISER | | | SHOWS 5KW BUT CUT SHEETS SHOW 9.8KW ??? | | | | | | 4) BACKUP PANEL CUTSHEETS AND PANEL SCHEDULE. | | | | | | 5) OCP FOR BATTERY WHERE IS IT AND WHAT SIZE IS IT, |
|