Plan Review Notes
Plan Review Notes For Permit 19121054
Permit Number 19121054
Review Stop B
Sequence Number 1
Notes
Date Text
2019-12-30 08:56:49 
 ***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561?805?6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 THE SUBMITTED FLAME SPREAD TEST REPORT (ASTM E?84) WAS
 TESTED AND APPROVED FOR WOOD FLOORING.
  
 PLEASE PROVIDE THE APPROVED (ASTM E?84) TEST REPORT AND
 RESULTS FOR USING ECO?ULTIMATE SILENCER UNDERLAYMENT
 WITH LAMINATE FLOORING OR SUBMIT A DIFFERENT PRODUCT
 THAT HAS BEEN TESTED AND APPROVED WITH LAMINATE
 FLOORING SUCH AS PROFLEX LV200.