| Plan Review Notes For Permit 19121053 |
| Permit Number |
19121053 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-12-30 08:48:49 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. | | | THE SUBMITTED FLAME SPREAD TEST REPORT (ASTM E-84) WAS | | | TESTED AND APPROVED FOR WOOD FLOORING. | | | PLEASE PROVIDE THE APPROVED (ASTM E-84) TEST REPORT AND | | | RESULTS FOR USING ECO-ULTIMATE SILENCER UNDERLAYMENT | | | WITH LAMINATE FLOORING OR SUBMIT A DIFFERENT PRODUCT | | | THAT HAS BEEN TESTED AND APPROVED WITH LAMINATE | | | FLOORING SUCH AS PROFLEX LV200. | | | |
|