| 2020-01-02 18:55:09 | 01/02/2020 1ST POOL REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. POOL GAS HEATER DOES NOT HAVE THE MODEL OR SIZE, |
| | PLEASE PROVIDE ON SHEET 1 OR HIGHLIGHT ON SPECS PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | 2. THE POOL HEATER SHALL HAVE A MINIMUM THERMAL |
| | EFFICIENCY OF 82% PER THE 2017 FBC-ENERGY SEC. |
| | R403.10.4. |
| | 3. THERE IS A COLLECTOR TANK ON A RESIDENTIAL POOL, |
| | PLEASE CLARIFY THE REASON FOR THE INSTALLATION OF THIS |
| | APERTURE ON THIS SYSTEM PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 4. MAIN DRAIN SYSTEM AND SERVICE OVERFLOW SYSTEMS WITH |
| | DISCHARGE TO COLLECTOR TANKS SHALL BE SIZED A MAXIMUM |
| | 3' PER SECOND AND IT IS SHOWING 3.9' PER SECOND AS IT |
| | NEEDS TO MEET THE SAME CRITERIA OF THE CODE PER THE |
| | 2017 FBC SEC. 454.1.6.5.8 SWIMMING POOLS AND BATHING |
| | PLACES (PUBLIC AND PRIVATE) . |
| | 5. DOES THE COLLECTOR TANK HAVE A DRAINING SYSTEM AND |
| | HOW IS THE COLLECTOR TANK GOING TO BE CLEAN OR |
| | SERVICED, PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | 561-805-6720 |
| | |
| | |