| Date |
Text |
| 2020-01-12 17:43:24 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND |
| | SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE |
| | ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS |
| | 471.003(2)(H); 471.025; WPB FBC 107.1 |
| | |
| | 2. EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER |
| | CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE |
| | LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY |
| | OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL |
| | UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN NEC |
| | 600.6(A)(1) |
| | |
| | 3. ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 405.1 |
| | SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT |
| | OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & |
| | TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME |
| | SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING |
| | DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. |
| | FBC-EC 405.2.5 |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |