2020-01-27 08:44:10***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 1) FBC EB 402.1/811.1 & FBC EC R 502.1; PROVIDE ENERGY
 & A/C CALCULATIONS INCLUDING NEW DOORS/WINDOWS/WALLS.
  
 2) FBC B 1072.1/107.2.5; PROVIDE SURVEY EITH
 MEASUREMENTS AND SET- BACKS TO ADDITION.
  
 3) FBC B 109.3; THE VALUATION APPEARS TO BE VERY LOW.
 RE-EVALUATE, THE VALUE MUST BE WITHIN THE RANGE OF THE
 INDUSTRY STANDARD.
  
 4) FBC B 107.2.1; PROVIDE THE WINDOW AND DOOR PRODUCT
 APPROVALS (REVIEW STAMPED/SIGNED BY DESIGNER OF
 RECORD).
  