2020-03-17 08:06:18SEE NFIP REVIEW. CT
2020-03-03 11:17:45PLAN REVIEW - NFIP ELEVATION CERTIFICATE
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS FROM 1ST REVIEW HAVE NOT BEEN
 ADDRESSED:
  
  
 ELEVATION CERTIFICATE REVIEW:
  
 1) A7 VERIFY THAT THIS IS 1A AS ENTERED BECAUSE THE
 PLANS SHOW STEM WALL CONSTRUCTION AND THAT FITS BETTER
 WITH DIAGRAM 1B.
  
 2) A9(B) PLEASE ENTER NUMBER OF FLOOD OPENINGS IN
 ATTACHED GARAGE. (PLANS SHOW 4)
  
 3) A9(C) ENTER NET AREA OF OPENINGS.PLANS SAY MODEL
 1540-520. PRODUCT APPROVAL FL58822-R3 SHOWS MODEL
 1540-520 AT .53 SQ. FT. PER VENT.
  
 4) A9(D) THESE ARE ENGINEERED OPENINGS USING ENGINEERED
 PRODUCT UNDER PRODUCT APPROVAL FL58822-R3
  
 5) PLEASE STATE IN COMMENTS WHAT VERTICAL DATUM WAS
 UTILIZED FOR A5.
  
 NEW COMMENT:
  
 UPON SUBMITTAL OF FINISHED CONSTRUCTION ELEVATION
 CERTIFICATE, PROVIDE THE FOLLOWING INFORMATION:
  
 6) C2 (E) LOWEST ELEVATION OF MACHINERY OR EQUIPMENT
 SERVICING THE BUILDING SHALL BE AT OR ABOVE DFE OF 9.0
 FEET NAVD
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  