| Plan Review Notes For Permit 19120988 |
| Permit Number |
19120988 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-12-24 10:09:49 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 19120988 | | | REVIEWED: DECEMBER 24, 2019 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | | | | FLORIDA BUILDING CODE,6TH EDITION (2017) | | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC[R] = FBC RESIDENTIAL | | | | | | ELEVATION CERTIFICATE REVIEW: | | | | | | 1) A7 VERIFY THAT THIS IS 1A AS ENTERED BECAUSE THE | | | PLANS SHOW STEM WALL CONSTRUCTION AND THAT FITS BETTER | | | WITH DIAGRAM 1B. | | | | | | 2) A9(B) PLEASE ENTER NUMBER OF FLOOD OPENINGS IN | | | ATTACHED GARAGE. (PLANS SHOW 4) | | | | | | 3) A9(C) ENTER NET AREA OF OPENINGS.PLANS SAY MODEL | | | 1540-520. PRODUCT APPROVAL FL58822-R3 SHOWS MODEL | | | 1540-520 AT .53 SQ. FT. PER VENT. | | | | | | 4) A9(D) THESE ARE ENGINEERED OPENINGS USING ENGINEERED | | | PRODUCT UNDER PRODUCT APPROVAL FL58822-R3 | | | | | | 5) PLEASE STATE IN COMMENTS WHAT VERTICAL DATUM WAS | | | UTILIZED FOR A5. | | | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | | [email protected] | | | | | | | | | | | | |
|