2020-01-17 15:22:08NOTE:NONE OF THE COMMENTS FROM THE PREVIOUS REVIEW HAVE
 BEENADDRESSED.
  
 1) A REDUCED PRESSURE ZONE (RPZ) BACKFLOW PREVENTION
 DEVICE IS REQUIRED AT THE WATER METER FOR THE
 IRRIGATION SYSTEM PER THE CITY OF WEST PALM
 CROSS-CONNECTION CONTROL MANUAL AS ADOPTED BY CITY
 ORDINANCE.PRESSURE VACUUM BREAKERS ARE ONLY PERMITTED
 TO BE USED ON ONE AND TWO FAMILY DWELLINGS.
 2)THE BACKFLOW DEVICE SHALL BE LEAD FREE PER THE CITY
 OF WEST PALM CROSS-CONNECTION CONTROL MANUAL AS ADOPTED
 BY CITY ORDINANCE AND SEC. 605.2 OF THE 2017
 FBC-PLUMBING.
 3) A SEPARATE PERMIT WILL BE REQUIRED FOR THE BACKFLOW
 DEVICE. TWO COPIES OF THE MANUFACTURER'S SPECIFICATIONS
 SHALL BE SUBMITTED ALONG WITH A PERMIT APPLICATION
 FORM.
 4) IDENTIFY THE LOCATION OF THE WATER METER ON THE
 PLANS. WPB AMEND. TO FBC SEC.107.2.1. THE BACKFLOW
 DEVICE SHALL BE LOCATED AS CLOSE AS POSSIBLE TO THE
 WATER METER PER THE CITY OF WEST PALM CROSS-CONNECTION
 CONTROL MANUAL AS ADOPTED BY CITY ORDINANCE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  