| Plan Review Notes For Permit 19120975 |
| Permit Number |
19120975 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-12-27 04:38:10 | 1) A REDUCED PRESSURE ZONE (RPZ) BACKFLOW PREVENTION | | | DEVICE IS REQUIRED AT THE WATER METER FOR THE | | | IRRIGATION SYSTEM PER THE CITY OF WEST PALM | | | CROSS-CONNECTION CONTROL MANUAL AS ADOPTED BY CITY | | | ORDINANCE.PRESSURE VACUUM BREAKERS ARE ONLY PERMITTED | | | TO BE USED ON ONE AND TWO FAMILY DWELLINGS. | | | 2)THE BACKFLOW DEVICE SHALL BE LEAD FREE PER THE CITY | | | OF WEST PALM CROSS-CONNECTION CONTROL MANUAL AS ADOPTED | | | BY CITY ORDINANCE AND SEC. 605.2 OF THE 2017 | | | FBC-PLUMBING. | | | 3) A SEPARATE PERMIT WILL BE REQUIRED FOR THE BACKFLOW | | | DEVICE. TWO COPIES OF THE MANUFACTURER'S SPECIFICATIONS | | | SHALL BE SUBMITTED ALONG WITH A PERMIT APPLICATION | | | FORM. | | | 4) IDENTIFY THE LOCATION OF THE WATER METER ON THE | | | PLANS. WPB AMEND. TO FBC SEC.107.2.1. THE BACKFLOW | | | DEVICE SHALL BE LOCATED AS CLOSE AS POSSIBLE TO THE | | | WATER METER PER THE CITY OF WEST PALM CROSS-CONNECTION | | | CONTROL MANUAL AS ADOPTED BY CITY ORDINANCE. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|