Plan Review Notes
Plan Review Notes For Permit 19120949
Permit Number 19120949
Review Stop B
Sequence Number 2
Notes
Date Text
2020-02-19 18:00:01RESIDENTIAL (R3) ALTERATION SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO
 ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR
 IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1- ENERGY CALCULATIONS SUBMITTED:
 A)OK
  
 ORIGINAL COMMENT:
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME,
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 ORIGINAL COMMENT:
 C) PROVIDE CORRECT INFORMATION ON ITEM #1 ON PAGE 1 OF
 4. THIS IS NOT NEW CONSTRUCTION. THIS IS AN EXISTING
 HOUSE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 ORIGINAL COMMENT:
 D) REVISE COOLING INFORMATION ON ITEM #12 ON PAGE 1 OF
 4 TO MATCH PLANS AND COOLING EQUIPMENT INFORMATION
 SUBMITTED. THE SEER OF THIS EQUIPMENT IS 14.50 NOT 16.
 REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 IT IS NOT CLEAR HOW THE SEER OF THE EQUIPMENT WAS
 CHANGED. PAGE 1 OF 4 SHOWS 14.5 SEER BUT THE FINAL
 RESULTS DIDN'T CHANGE. THE TOTAL PROPOSED MODIFIED
 LOADS (36.27) AND THE TOTAL BASELINE LOADS (40.62)
 STAYED THE SAME AS THE OLD ENERGY CALCULATIONS THAT
 WERE SUBMITTED EARLIER. THIS IS A COMPUTER GENERATED
 PROGRAM. ANY CHANGES WILL RESULT IN CHANGES ON THE
 FINAL OUTPUT. CLARIFY/REVISE AS REQUIRED. ORIGINAL
 COMPUTER GENERATED ENERGY CALCULATIONS NEED TO BE
 REVISED. (NOTE: OWNER TOOK ONE COPY OF THE OLD ENERGY
 CALCULATIONS AND THE NEW ENERGY CALCULATIONS THAT WERE
 RESUBMITTED TO TAKE BACK TO THE PERSON WHO DID THE
 ENERGY CALCULATIONS).
 IN ADDITION, AFTER TALKING TO THE MR. BARIS (OWNER) WE
 FOUND OUT THAT THE EQUIPMENT SIZE SHOWN ON THE ENERGY
 CALCULATIONS (1-1/2 TON.) DOESN'T MATCH THE EQUIPMENT
 SIZE SHOWN ON THE A/C PLAN (3.5 TON). REVISE AS
 REQUIRED TO MATCH TO AVOID CONFLICTS/DELAYS.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 ORIGINAL COMMENT:
 E) DOORS INFORMATION ON PAGE 3 OF 4 IS INCORRECT. THERE
 ARE NOT 3 EXTERIOR DOORS. SEE PROPOSED PLAN AND REVISE
 AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 ORIGINAL COMMENT:
 F) WINDOWS INFORMATION ON PAGE 3 OF 4 IS INCORRECT. THE
 WINDOWS FRAME IS PVC NOT METAL. SEE WINDOW SCHEDULE ON
 ENGINEERED DRAWING 2.0 AND PRODUCT APPROVALS SUBMITTED
 AND REVISE AS REQUIRED. ALSO, REVISE WINDOW AREAS TO
 MATCH PLANS. NOTE: COORDINATE WITH DOOR INFORMATION
 COMMENT #1(E) ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 ORIGINAL COMMENT:
 2- SPECIFY THE SIZE AND TYPE OF EXISTING WINDOW AND
 SIZE AND TYPE OF PROPOSED WINDOWS TO VERIFY COMPLIANCE
 WITH THE EGRESS REQUIREMENTS OF SEC. 702.5 FBC-EXISTING
 BUILDING.
  
 RESPONSE:
 THIS IS OK. SEE CURRENT PERMIT #19100358 FOR WINDOW
 REPLACEMENT. INSPECTIONS FOR WINDOWS ARE CURRENTLY DONE
 UNDER THIS PERMIT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  