Plan Review Notes
Plan Review Notes For Permit 19120949
Permit Number 19120949
Review Stop M
Sequence Number 1
Notes
Date Text
2020-01-16 14:50:391ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19120949
 1/16/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE OWNER/AGENT SHALL SIGN AND DATE THE ENERGY
 EFFICIENCY COMPLIANCE FORM R405-2017- SECTION
 R103.1.1.2 FBC EC.
  
 2) PROVIDE PRODUCT DATA SHEETS FOR THE NEW WINDOWS TO
 VERIFY THE U-FACTOR AND 0.25 SHGC VALUES LISTED ON THE
 ENERGY FORM- R405.3 FBC EC.
  
 3) R30 UNDER ATTIC INSULATION IS SHOWN ON THE ENERGY
 FORM. PLEASE PROVIDE A SECTION DRAWING OR NOTE OR THE
 PLAN TO VERIFY COMPLIANCE- SECTION R405.3 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  