| Date |
Text |
| 2020-01-16 14:50:39 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19120949 |
| | 1/16/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE OWNER/AGENT SHALL SIGN AND DATE THE ENERGY |
| | EFFICIENCY COMPLIANCE FORM R405-2017- SECTION |
| | R103.1.1.2 FBC EC. |
| | |
| | 2) PROVIDE PRODUCT DATA SHEETS FOR THE NEW WINDOWS TO |
| | VERIFY THE U-FACTOR AND 0.25 SHGC VALUES LISTED ON THE |
| | ENERGY FORM- R405.3 FBC EC. |
| | |
| | 3) R30 UNDER ATTIC INSULATION IS SHOWN ON THE ENERGY |
| | FORM. PLEASE PROVIDE A SECTION DRAWING OR NOTE OR THE |
| | PLAN TO VERIFY COMPLIANCE- SECTION R405.3 FBC EC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |