2020-01-17 17:42:58RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO
 ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR
 IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1- ENERGY CALCULATIONS SUBMITTED:
 A)ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED
 AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 6TH EDITION
 (2017).
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME,
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) PROVIDE CORRECT INFORMATION ON ITEM #1 ON PAGE 1 OF
 4. THIS IS NOT NEW CONSTRUCTION. THIS IS AN EXISTING
 HOUSE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) REVISE COOLING INFORMATION ON ITEM #12 ON PAGE 1 OF
 4 TO MATCH PLANS AND COOLING EQUIPMENT INFORMATION
 SUBMITTED. THE SEER OF THIS EQUIPMENT IS 14.50 NOT 16.
 REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E) DOORS INFORMATION ON PAGE 3 OF 4 IS INCORRECT. THERE
 ARE NOT 3 EXTERIOR DOORS. SEE PROPOSED PLAN AND REVISE
 AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F) WINDOWS INFORMATION ON PAGE 3 OF 4 IS INCORRECT. THE
 WINDOWS FRAME IS PVC NOT METAL. SEE WINDOW SCHEDULE ON
 ENGINEERED DRAWING 2.0 AND PRODUCT APPROVALS SUBMITTED
 AND REVISE AS REQUIRED. ALSO, REVISE WINDOW AREAS TO
 MATCH PLANS. NOTE: COORDINATE WITH DOOR INFORMATION
 COMMENT #1(E) ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
  
 2- SPECIFY THE SIZE AND TYPE OF EXISTING WINDOW AND
 SIZE AND TYPE OF PROPOSED WINDOWS TO VERIFY COMPLIANCE
 WITH THE EGRESS REQUIREMENTS OF SEC. 702.5 FBC-EXISTING
 BUILDING.
  
 NOTE: NEED TO VERIFY MANUFACTURER'S LARGEST STANDARD
 SIZE WINDOW THAT WILL FIT WITHIN THE EXISTING FRAME OR
 EXISTING ROUGH OPENING AND THAT WILL NOT REDUCE THE
 EGRESS SIZE OPENING OF EXISTING WINDOW AS REQUIRED BY
 SEC. 702.5 FBC-EXISTING BUILDING.
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,