| 2019-12-31 18:47:11 | 12/31/2019 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | 2. PLUMBING RISER DIAGRAM REQUIRED PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.3.5.3 (11) RESIDENTIAL |
| | PLUMBING. |
| | |
| | 3. KITCHEN CANNOT DRAIN DOWNSTREAM OF A WET VENT PER |
| | THE 2017 FBC SEC. R3108.2.2 |
| | |
| | 4. SIGNATURE (OR SEAL, OR TITLE BLOCK, OR ALL THREE) |
| | ARE NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.001, FLORIDA STATUTE 471. |
| | |
| | 5. PLANS ARE DIGITALLY SIGNED AND SEAL. ONLY WHEN THE |
| | PLANS ARE SUBMITTED DIGITALLY IS THIS ALLOWED. |
| | 61G15-23.005. PLANS SUBMITTED IN PAPER FORM ARE |
| | REQUIRED TO BE SEALED AND WET SIGNED BY THE DESIGN |
| | PROFESSIONAL. 61G15-23.001. |
| | |
| | 6. WASHING MACHINE STANDPIPE DRAIN PER MANUFACTURES |
| | SPECIFICATION MAY CALL OUT A 3" DRAIN SO PLEASE SIZE |
| | ACCORDINGLY. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | |