Plan Review Notes
Plan Review Notes For Permit 19120904
Permit Number 19120904
Review Stop M
Sequence Number 1
Notes
Date Text
2020-01-16 17:22:341ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19120904
 1/16/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 4: PROVIDE AN AC EQUIPMENT SCHEDULE- SECTION
 107.2.1 WPB AND TABLE C403.2.3(1) FBC EC.
  
 2) SHEET 4: RETURN AIR SYSTEM NOT SHOWN ON THE PLAN-
 SEE SECTION M1602.2 & M1602.3 FBC RES.
  
 3) SHEET 4: EXHAUST VENTILATION SYSTEMS REQUIRED FOR
 THE KITCHEN AND BATHS- SEE TABLE M1507.4FBC RES FOR
 REQUIRED EXHAUST RATES.
  
 4) SHEET 4: PROVIDE DRYER EXHAUST DETAILS. SHOW THE
 EXHAUST DUCT RUN AND TERMINATION LOCATION. INDICATE
 TYPE AND SIZE OF DUCT- SECTION M1502.4 FBC RES.
  
 5) PROVIDE MANUAL J AC COOLING AND HEATING
 CALCULATIONS- SECTION R403.7.1 FBC RES.
  
 6) PROVIDE AN ENERGY CONPLIANCE REPORT FOR THE NEW
 ADDITION- SECTION R101.5.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  