| 2020-01-16 17:22:34 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19120904 |
| | 1/16/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET 4: PROVIDE AN AC EQUIPMENT SCHEDULE- SECTION |
| | 107.2.1 WPB AND TABLE C403.2.3(1) FBC EC. |
| | |
| | 2) SHEET 4: RETURN AIR SYSTEM NOT SHOWN ON THE PLAN- |
| | SEE SECTION M1602.2 & M1602.3 FBC RES. |
| | |
| | 3) SHEET 4: EXHAUST VENTILATION SYSTEMS REQUIRED FOR |
| | THE KITCHEN AND BATHS- SEE TABLE M1507.4FBC RES FOR |
| | REQUIRED EXHAUST RATES. |
| | |
| | 4) SHEET 4: PROVIDE DRYER EXHAUST DETAILS. SHOW THE |
| | EXHAUST DUCT RUN AND TERMINATION LOCATION. INDICATE |
| | TYPE AND SIZE OF DUCT- SECTION M1502.4 FBC RES. |
| | |
| | 5) PROVIDE MANUAL J AC COOLING AND HEATING |
| | CALCULATIONS- SECTION R403.7.1 FBC RES. |
| | |
| | 6) PROVIDE AN ENERGY CONPLIANCE REPORT FOR THE NEW |
| | ADDITION- SECTION R101.5.1 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |