Plan Review Notes
Plan Review Notes For Permit 19120885
Permit Number 19120885
Review Stop E
Sequence Number 2
Notes
Date Text
2020-04-22 08:13:36CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. LOAD CALCULATION PROVIDED EXCEEDS THE CAPACITY OF
 THE SERVICE AND THE NEW PANEL SPECIFIED ON RISER
 DIAGRAM. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. THIS LOAD CALCULATION SHOULD BE IN
 THE FORMAT SPECIFIED IN THE FBC RESIDENTIAL. NEC 215.2,
 220, 408.30; FBC RE E3602.2 (NOT PROVIDED OR
 CORRECTED.)
 2. PROVIDE CORRECTIONS TO ANY SERVICE EQUIPMENT THAT IS
 UNDERSIZED. NEC 110.3, 215.2, 240.4, 408.30 (NOT
 CORRECTED. MAIN BREAKER IN RISER STILL SHOWS AS 100
 AMP.)
 3. IF SERVICE IS TO BE UPGRADED, PROVIDE AVAILABLE
 SHORT CIRCUIT CALCULATION FOR SERVICE INCLUDING
 INFORMATION FROM THE POWER COMPANY STATING WHAT THE
 AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE SERVICE TO
 CONFIRM THE STATED AIC RATING OF THE SERVICE EQUIPMENT
 IS ADEQUATE. NEC 110.9, 110.10; FBC RE E3606.3 (NOT
 PROVIDED OR ADDRESSED.)
 4. CORRECTED.
 5. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  