| 2020-01-03 09:25:33 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) PROVIDE TWO SETS OF A GENERATOR PAD DETAIL DRAWING. | | | SPECIFY THE LENGTH, WIDTH AND THICHNESS OF THE CONCRETE | | | SLAB. SPECIFY THE STEEL REINFORCING IN THE SLAB AND THE | | | TYPE AND SIZE OF THE ANCHORS THAT WILL ATTACH THE | | | GENERATOR TO THE SLAB. SOME OF THIS INFORMATION WAS | | | PROVIDED ON THE ELECTRIAL PLANS. NOTE #1 ON PAGE 8 OF | | | THE GENERAC INSTALLATION LAYOUT LISTS THE RECOMMENDED | | | CONCRETE PAD SIZE. PLEASE PROVIDE ALL OF THIS | | | INFORMATION ON THE GENERATOR PAD DETAIL DRAWINGS ALONG | | | WITH THE PROPERTY ADDRESS AND THE PRINTED NAME AND | | | SIGNATURE OF THE PERSON THAT DID THE DRAWING. FBC | | | 107.2.1 | | | |
|