| Notes |
| Date |
Text |
| 2020-01-03 10:01:29 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PAD DIMENSIONS THAT ARE SPECIFIED ON THE | | | ELECTRICAL DRAWINGS ARE SMALLER THAN THE MINIMUM | | | RECOMMENDED CONCRETE PAD SIZE IN NOTE #1 ON PAGE 9 OF | | | THE GENERAC INSTALLATION LAYOUT. FBC 107.2.1 |
|