| 2020-01-17 12:39:03 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19120856 |
| | REVIEWED: JANUARY 17, 2020 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| | BELOW) |
| | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| | BUILDING-PERMIT-FORMS |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 1) 501.1.1 FBC[RE] ADDITIONS, ALTERATIONS, OR REPAIRS: |
| | GENERAL. ADDITIONS, ALTERATIONS, OR REPAIRS TO AN |
| | EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF |
| | SHALL COMPLY WITH SECTION R502, R503 OR R504. UNALTERED |
| | PORTIONS OF THE EXISTING BUILDING OR BUILDING SUPPLY |
| | SYSTEM SHALL NOT BE REQUIRED TO COMPLY WITH THIS CODE. |
| | - PROVIDE PERFORMANCE BASED ENERGY CALCULATIONS TO |
| | INCLUDE NEW CLOSET AND ANY ADJUSTMENTS IN FENESTRATION. |
| | IF USING PRESCRIPTIVE THAN NOTE THAT ON PLANS AND AND |
| | R-VALUES AT WALLS/CEILINGS AND INCLUDE SHGF FOR NEW |
| | OPENINGS. |
| | |
| | 2) 503.1.1 FBC[E] BUILDING ENVELOPE ASSEMBLIES THAT ARE |
| | PART OF THE ALTERATION SHALL COMPLY WITH SECTION |
| | R402.1.2 OR R402.1.4, SECTIONS R402.2.1 THROUGH |
| | R402.2.13, R402.3.1, R402.3.2, R402.4.3 AND R402.4.5 |
| | - IN-FILL DETAILS SHOULD SHOW INSULATION TO BE USED. |
| | |
| | 3) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| | ACCESS DOORS INTO GARAGE AND ROLLUP GARAGE DOOR, OR |
| | INDICATE THAT YOU WOULD LIKE THEM DEFERRED. |
| | |
| | 4) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| | ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM DEFERRED. |
| | |
| | 5) 107.3.4.1 FBC[AMENDED] SUBMIT TRUSS SHOP DRAWINGS TO |
| | THE BUILDING INSPECTOR PRIOR TO INSTALLATION. |
| | - THE TRUSS SUBMITTAL CAN BE APPROVED NOW IF PUT IN |
| | SUPPORTING DOCUMENTS AS A SUBMITTAL, OR IT CAN BE |
| | DEFERRED. IF DEFERED THE TRUSS PACKAGE NEEDS TO BE |
| | REVIEWED BY BUILDING INSPECTOR PRIOR TO INSTALLATION. |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |