2020-01-22 16:58:11BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19120853
 REVIEWED: JANUARY 22, 2020
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 107.2.5 FBC[AMENDED] DEMOLITION PLAN.
 - PROVIDE DEMOLITION PLAN TO SHOW EXISTING
 CONFIGURATION, AREA AND DIMENSIONS.
  
 2) 109.3 FBC[AMENDED] PROVIDE BREAKDOWN OF WHAT THE
 PROJECT VALUE WOULD BE IF THE WORK WAS PERFORMED BY
 HIRED CONTRACTORS. EVEN THOUGH THIS IS OWNER/BUILDER,
 THE BUILDING DEPARTMENT ASSESSES FEES BASED ON
 MATERIALS AND LABOR AS WE DO PLAN REVIEWS AND
 INSPECTIONS BASED ON ACTUAL CONSTRUCTION COSTS.
  
 3) 107.5.3 FBC[AMENDED] STATE THE CODE EDITION THAT
 APPLY TO THIS PROJECT
 - FLORIDA BUILDING CODE(FBC), 6TH EDITION (2017)
 BUILDING, MECHANICAL, PLUMBING AND NATIONAL ELECTRIC
 CODE (NFPA 70)2014
  
 4) LEVEL 2 ALTERARTION
 - STATE ON PLANS THAT THIS IS A LEVEL 2 ALTERATION
  
 5) SQUARE FOOTAGE
 - STATE ON PLANS WHAT THE EXISTING SQUARE FOOTAGE WAS.
 (CARPORT NON-CONDITIONED) AND WHAT THE SQUARE FOOTAGE
 IS NOW (CONDITIONED HABITABLE SPACE)
  
 6) R314.3 FBC[R] LOCATION. SMOKE ALARMS SHALL BE
 INSTALLED IN THE FOLLOWING LOCATIONS:
  
 1. IN EACH SLEEPING ROOM.
  
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
  
 7) 501 FBC[ENERGY]STATE ON PLANS HOW THE ENERGY CODE IS
 BEING MET FOR ALTERATIONS. R- VALUE OF INSULATION IN
 WALLS AND CEILING.
 - ALSO, SWHO ANY OPENINGS INCLUDING WINDOWS.
  
 8) 310.1 FBC[R]EMERGENCY ESCAPE AND RESCUE OPENING
 REQUIRED. BASEMENTS, HABITABLE ATTICS AND EVERY
 SLEEPING ROOM SHALL HAVE NOT LESS THAN ONE OPERABLE
 EMERGENCY ESCAPE AND RESCUE OPENING. WHERE BASEMENTS
 CONTAIN ONE OR MORE SLEEPING ROOMS, AN EMERGENCY ESCAPE
 AND RESCUE OPENING SHALL BE REQUIRED IN EACH SLEEPING
 ROOM. EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL OPEN
 DIRECTLY INTO A PUBLIC WAY, OR TO A YARD OR COURT THAT
 OPENS TO A PUBLIC WAY.
  
 310.2.1 FBC[R] MINIMUM OPENING AREA EMERGENCY AND
 ESCAPE RESCUE OPENINGS SHALL HAVE A NET CLEAR OPENING
 OF NOT LESS THAN 5.7 SQUARE FEET. THE NET CLEAR OPENING
 DIMENSIONS REQUIRED BY THIS SECTION SHALL BE OBTAINED
 BY THE NORMAL OPERATION OF THE EMERGENCY ESCAPE AND
 RESCUE OPENING FROM THE INSIDE. THE NET CLEAR HEIGHT
 OPENING SHALL BE NOT LESS THAN 24 INCHES AND THE NET
 CLEAR WIDTH SHALL BE NOT LESS THAN 20 INCHES.
 - MARK ON PLANS BEDROOM WINDOWS TO MEET EGRESS
 REQUIREMENTS.
  
 9) 318.1 FBC[R] TERMITE PROTECTION. TERMITE PROTECTION
 SHALL BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING
 SOIL APPLIED PESTICIDES, BAITING SYSTEMS, AND
 PESTICIDES APPLIED TO WOOD, OR OTHER APPROVED METHODS
 OF TERMITE PROTECTION LABELED FOR USE AS A PREVENTATIVE
 TREATMENT TO NEW CONSTRUCTION. SEE SECTION 202,
 ?REGISTERED TERMITICIDE.? UPON COMPLETION OF THE
 APPLICATION OF THE TERMITE PROTECTIVE TREATMENT, A
 CERTIFICATE OF COMPLIANCE SHALL BE ISSUED TO THE
 BUILDING DEPARTMENT BY THE LICENSED PEST CONTROL
 COMPANY THAT CONTAINS THE FOLLOWING STATEMENT: ?THE
 BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE
 PREVENTION OF SUBTERRANEAN TERMITES. TREATMENT IS IN
 ACCORDANCE WITH RULES AND LAWS ESTABLISHED BY THE
 FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER
 SERVICES.?
  
 10) ASCE 7-10 26.7.1 WIND EXPOSURE CATEGORY.
 - THIS SITE WOULD BE EXPOSURE B
  
 11) 301.2.1.2 FBC[R] PROTECTION OF OPENINGS.
 - IF THE WINDOWS ARE NOT IMPACT RATED PLEASE PROVIDE
 HOW WINDOWS ARE BEING PROTECTED, IF SHUTTERS PROVIDE
 PRODUCT APPROVAL FOR THE SHUTTER SYSYTEM TO BE USED.
  
 12) 107.5.3 FBC[AMENDED]PROVIDE PRODUCT APPROVALS FOR
 ANY WINDOWS AND DOORS. PROVIDE SIZES OF ANY WINDOWS OR
 DOORS ON THE PLANS.
  
 13) 602.7.5 FBC[R] FULL HEIGHT STUDS AT OPENINGS.
 - PLEASE SHOW DETAILS OF WALL CONSTRUCTION.
 TYPE(MATERIALS), THICKNESS, CONNECTORS, SPACING AND HOW
 TIED TO EXISTING.
  
 317.19(5) FBC[R] WOOD SIDING, SHEATHING AND WALL
 FRAMING ON THE EXTERIOR OF A BUILDING HAVING A
 CLEARANCE OF LESS THAN 6 INCHES (152 MM) FROM THE
 GROUND OR LESS THAN 2 INCHES (51 MM) MEASURED
 VERTICALLY FROM CONCRETE STEPS, PORCH SLABS, PATIO
 SLABS AND SIMILAR HORIZONTAL SURFACES EXPOSED TO THE
 WEATHER.
  
 14) 317.1.2 FBC[R] GROUND CONTACT. ALL WOOD IN CONTACT
 WITH THE GROUND, EMBEDDED IN CONCRETE IN DIRECT CONTACT
 WITH THE GROUND OR EMBEDDED IN CONCRETE EXPOSED TO THE
 WEATHER THAT SUPPORTS PERMANENT STRUCTURES INTENDED FOR
 HUMAN OCCUPANCY SHALL BE APPROVED
 PRESSURE-PRESERVATIVE-TREATED WOOD SUITABLE FOR GROUND
 CONTACT USE, EXCEPT THAT UNTREATED WOOD USED ENTIRELY
 BELOW GROUNDWATER LEVEL OR CONTINUOUSLY SUBMERGED IN
 FRESH WATER SHALL NOT BE REQUIRED TO BE
 PRESSURE-PRESERVATIVE TREATED.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS.
 FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE
 REQUIRED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  