| Plan Review Notes For Permit 19120825 |
| Permit Number |
19120825 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-01-07 13:29:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE IS AN INDICATION OF A DDCV AND UNDERGROUND | | | FIRE LINE WORK | | | | | | ALL FIRE LINE UNDERGROUND SHALL BE SUBMITTED | | | UNDERPARATE PERMIT AND SHOP DRAWINGS AND COMPLY WITH | | | NFPA 24. | | | | | | THE WORK SHALL BE COMPLETED BY A CERTIFIED STATE OF | | | FLORIDA UNDERGROUND CONTRACTOR. | | | | | | PLEASE REVIEW AND COMPLY. | | | | | | | | | | | | 2) THERE ARE NO INDICATION OF THE TYPE OF COMMODITY | | | BEING PROTECTED, TYPE OF PALLETS, WRAPPINGS, STORAGE | | | HEIGHT, ETC. | | | | | | PLEASE REVIEW AND PROVIDE DETAILS. | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|