| | 2ND REVIEW FBC-2017 PLUMBING/GAS |
| | PERMIT #19120807 |
| | 4/30/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET 4, UNDERGROUND GAS PIPING: SHOW THE WHERE |
| | GENERATOR BRANCH LINE CONNECTS TO THE MAIN LINE- |
| | SECTION 107.2.1 WPB. |
| | |
| | 2) P1.1: MODIFY THE ISOMETRIC DRAWING TO INDICATE THE |
| | LENGTH OF THE UNDERGROUND PIPING RUN FROM THE POINT OF |
| | CONNECTION AT THE MAIN UNDERGROUND LINE TO THE NEW GAS |
| | METER AT THE ENCLOSURE. IDENTIFY THE TYPE AND SIZE OF |
| | UNDERGROUND GAS PIPING, BURIAL DEPTH AND HOW THE PIPE |
| | WILL BE PROTECTED FROM DAMAGE- SECTIONS 402.4 AND 404.1 |
| | FBC FG. |
| | |
| | 3) P1.1: I HAVE REVIEWED THE SUBMITTED SHOP DRAWINGS |
| | AND PRODUCT APPROVAL FOR THE GENERATOR ENCLOSURE, AND |
| | THE CLARKE GENERATOR SPECIFICATIONS SUBMITTAL WHICH |
| | INCLUDES THE OPTIBLEND DUEL FUEL SYSTEM SPECS. I DO NOT |
| | SEE IN ANY OF THESE DOCUMENTS AN INTERNAL GAS PIPING |
| | ISOMETRIC OR LAYOUT DRAWING FOR CONNECTING THE |
| | GENERATORS TO THE NEW EXTERIOR GAS LINE AND SERVICE. |
| | PAGE 29 OF THE GENERATOR SPECS INDICATES THE OPTIBLEND |
| | KITS ARE SHIPPED WITH EACH ASSEMBLY PACKAGE TOGETHER, |
| | BUT NO CONNECTION DETAILS PROVIDED TO THE GAS SUPPLY |
| | SYSTEM. PLEASE MODIFY THE EXISTING ISOMETRIC DRAWING |
| | ACCORDINGLY AND ALSO PROVIDE A GAS PIPING LAYOUT FOR |
| | INSIDE THE ENCLOSURE. SHOW LOCATIONS OF REGULATORS, |
| | SHUT OFF VALVES, UNIONS AND INLET PRESSURE REQUIRED AT |
| | THE OPTIBLEND KIT AND GENERATOR. PLEASE SEE GAS |
| | PRESSURE INFO ON PAGE 23 AND 29 OF THE SPEC- SECTIONS |
| | 107.2.1 WPB. A) PLEASE CLARIFY HOW THE 18,000 SCFH |
| | TOTAL GAS LOAD WAS DETERMINED. WHICH CONVERSION OR |
| | CALULATION METHOD WAS USED?- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |