| Plan Review Notes For Permit 19120807 |
| Permit Number |
19120807 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-04-24 16:33:41 | GENERATOR ENCLOSURE | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) BOTTOM HAND RAIL EXTENSION ON DRAWING 5.3 NEEDS TO | | | COMPLY WITH FBC 1014.6 HANDRAIL EXTENSIONS. "CONTINUE | | | TO SLOPE FOR THE DEPTH OF ONE TREAD BEYOND THE BOTTOM | | | RISER". | | | 2) GENERATOR HOUSING TIE DOWN (ATTACHMENT TO SLAB) | | | NEEDS TO BE A SITE SPECIFIC SIGNED AND SEALED DETAIL | | | SHOWING ATTACHMENT TYPE, SIZE, AMOUNT ETC. AND THE WIND | | | DESIGN CRITERIA USED FOR DESIGN - FROM AN ARCHITECT OR | | | ENGINEER TO COMPLY WITH WIND PRESSURES PER FBC 1609 | | | (180MPH) | | | |
|