| 2020-02-21 09:11:50 | |
| | GAS 1ST REVIEW**DENIED**19120807 |
| | |
| | |
| | 1)ON SHT. P1 YOU SO A NEW GAS METER BUT ALSO A GAS LINE |
| | TO CONNECT INTO THE BUILDINGS EXISTING. PLEASE CLARIFY. |
| | FBC 107.2.1. THE PLANS INDICATE AN EXISTING GAS METER. |
| | THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED |
| | INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE |
| | EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE |
| | EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE |
| | OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM |
| | THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD |
| | OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO |
| | EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH |
| | OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. |
| | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 |
| | |
| | |
| | 2)SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL |
| | GAS, SECS. 402.4.1, 402.4.2 SHOW THE TYPE OF PIPE |
| | MATERIAL BEING INSTALLED, ALL PIPE SIZES, AND THE |
| | CORRESPONDING EHD NUMBER OF THE |
| | |
| | |
| | |
| | |
| | |
| | 3)SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE, |
| | TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING |
| | DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL GAS SECS. |
| | 502 THRU 505 |
| | |
| | |
| | |
| | |
| | |
| | 4) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIMES |
| | |
| | |
| | |
| | |
| | |
| | 5)SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| | GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| | THRU 402.4 (37)E OF INSPECTION. FGC SEC.305.1 |
| | |
| | |
| | |
| | |
| | |
| | 6) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| | AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS |
| | SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4. |
| | |
| | |
| | 7) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. 2017 FGC SEC.410.1 |
| | |
| | |
| | 8) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE |
| | APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1 |
| | |
| | |
| | |
| | |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | |
| | |
| | |
| | |