| Plan Review Notes For Permit 19120807 |
| Permit Number |
19120807 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-02-18 10:59:28 | GENERATOR ENCLOSURE | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - | | | 1) PLEASE SHOW STAIRWAY HANDRAIL EXTENSIONS AT TOP AND | | | BOTTOM OF STAIRS TO COMPLY WITH FBC 1014.6 | | | 2) PLEASE PROVIDE STATE APPROVED PRE MANUFACTURED | | | BUILDING DRAWINGS APPROVED BY A THIRD PARTY REVIEW OR | | | SIGNED AND SEALED DRAWINGS FOR THE ON SITE CONSTRUCTION | | | OF THE ENCLOSURE FBC WPB AMENDMENTS 107.3 EXCEPTION (1) | | | 3) PLEASE PROVIDE A SIGNED AND SEALED SOIL REPORT FBC | | | 1803.1 | | | 4) PLEASE PROVIDE SIGNED AND SEALED ANCHORING DETAILS | | | FOR THE PRE FAB BUILDING AND STAIR - SHOW TYPE, SIZE | | | AND LOCATION OF ANCHORS. FBC WPB AMENDMENTS 107 | | | |
|