| Plan Review Notes For Permit 19120806 |
| Permit Number |
19120806 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-01-29 09:33:23 | 1) THE ARCHITECTURAL PLANS ARE REQUIRED TO BE | | | ELECTRONICALLY SIGNED AND SEALED PER FL. ADMIN. CODE | | | RULE 61G1-16.005. | | | 2) SUBMIT A KITCHEN EQUIPMENT SCHEDULE FOR THE KITCHEN | | | EQUIPMENT. WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) TEMPERED WATER IS REQUIRED AT THE LAVATORIES IN THE | | | RESTROOMS. ALL OTHER SINKS SHALL HAVE HOT WATER. THE | | | PLUMBING FIXTURE CONNECTION SCHEDULE CALLS OUT THE | | | TEMPERING DEVICES FOR THE LAVATORIES. 2017 FBC-PLUMBING | | | SEC.416.5. | | | 4) THE EXISTING CONCRETE GREASE INTERCEPTOR SHALL BE | | | PUMPED OUT AND INSPECTED FOR INTEGRITY BY THE PLUMBING | | | INSPECTOR. 2017 FBC SEC. 1003.10. | | | 5) THE HOT WATER RECIRCULATION LINE SHALL BE INSULATED | | | WITH A MINIMUM OF 1 INCH THICK INSULATION PER THE 2017 | | | FBC- ENERGY SEC.C403.2.10. | | | 6) THE SANITARY RISER DIAGRAM SHOWS CONDENSATE LINES | | | AND ICEMAKERS DISCHARGING INTO THE GREASY WASTER | | | SYSTEM. WASTES THAT DO NOT REQUIRE SEPARATION SHALL NOT | | | DISCHARGE TO GREASE INTERCEPTOR. | | | 7) SHT. P2.1 - SHOW THE SIZE OF THE THERMAL EXPANSION | | | TANK ON THE PLANS. WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|