| 2020-01-29 13:08:54 | 1) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE FLOOR |
| | FRYER. 2017 FBC-FUEL GAS SEC. 304.1. WHERE COMBUSTION |
| | AIR IS PROVIDED BY THE BUILDING?S MECHANICAL |
| | VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE |
| | SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE |
| | REQUIRED VENTILATION AIR. 2017 FBC-FUEL GAS |
| | SEC.304.9.3. |
| | 2) SUBMIT TWO COPIES OF THE MANUFACTURER?S |
| | SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND |
| | 301.3.GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC |
| | SEC.305.1, |
| | 3) SHT. P1.3 - SUBMIT A LEGEND FOR THE IDENTIFIERS G/1, |
| | G/2 G/3, ETC.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 4) THE MINIMUM SIZE PIPE TO THE GAS WATER HEATERS AT 45 |
| | FEET DEVELOPED LENGTH IS 1 1/4 INCHES BASED ON TABLE |
| | 402.4 (2). A MAXIMUM OF 284 MBTU CAN BE INSTALLED ON A |
| | ONE INCH LINE. |
| | 5) THE MINIMUM SIZE PIPE TO THE LAST GAS WATER HEATERS |
| | AT 45 FEET DEVELOPED LENGTH IS 1 INCH BASED ON TABLE |
| | 402.4 (2). A MAXIMUM OF 151 MBTU CAN BE INSTALLED ON A |
| | ONE INCH LINE. |
| | 6) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE |
| | INSTALLED WITHIN ONE (1) FOOT OF EITHER SIDE OF THE MP |
| | REGULATOR. 2017 FBC-FUEL GAS SEC. 410.2 (7). |
| | 7) EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE SHALL BE |
| | BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE |
| | UPSTREAM. UNION TO BE DOWN STREAM OF MANUAL VALVE. NFPA |
| | 96-14. SECS. 10.4.1, 10.4.3, 10.4.4, 10.5.1. |
| | 8) VENTS SHALL COMPLY WITH THE INSTALLATION MANUAL. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |