| Date |
Text |
| 2020-06-16 14:29:22 | PETER E VALENTI |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | FBC M = FBC MECHANICAL |
| | |
| | 4TH BUILDING REVIEW APPROVED WITH THE FOLLOWING |
| | PROVISOS: |
| | |
| | A) PROVIDE A REVISION FOR THE TYPE OF CONSTRUCTION THAT |
| | INCLUDES COMBUSTIBLE ROOF FRAMING OR INDICATES THE |
| | REQUIRED CHANGE TO NON-COMBUSTIBLE ROOF FRAMING AS PER |
| | TYPE OF CONSTRUCTION INDICATED. |
| | |
| | B) PROVIDE A REVISION FOR ADJUSTING THE 2ND FLOOR |
| | BATHROOM TO AN ACCESSIBLE BATHROOM AS PER NOTES |
| | INDICATED ON PAGE A4.0 DETAIL 2/A4.0. |
| | NOTE: THE 1ST FLOOR BATHROOM PLUMBING FIXTURE CLEAR |
| | FLOOR SPACE MUST COMPLY WITH THE FLORIDA ACCESSIBILITY |
| | CODE AS NOTED ON PAGE A4.0 DETAIL 1/A4.0. |
| | |
| | C) APPROVED WITH PROVISO: FBC B 107.3.4.1, PLEASE |
| | PROVIDE THE PRODUCT APPROVALS FOR ALLCOMPONENTS & |
| | CLADDING. 2017 FBC B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, ACM PANELS |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES. |
| | |
| | D) APPROVED WITH PROVISO: PLEASE PROVIDE WELDING AND |
| | BOLTING DOCUMENTATION IN ACCORDANCE WITH 2017 FBC?B |
| | 2204.1 WELDING |
| | 2017 FBC?B 2204.2 BOLTING. |
| | AWS D1.1 CLAUSE 3.1: AT TIME OF INSPECTION PLEASE |
| | PROVIDE A WELD PROCEDURE SPECIFICATION; THE W.P.S. |
| | SPECIFIES THE REQUIRED ESSENTIAL VARIABLES INCLUDING: |
| | BASE MATERIALS, JOINTS, PROCESS, AND FILLER METALS TO |
| | BE USED. |
| | AWS D1.1 CLAUSE 4.15: AT TIME OF INSPECTION PLEASE |
| | PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE |
| | W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO |
| | VERIFY THE WELDER?S QUALIFICATION AND CERTIFICATION AS |
| | IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT. |
| | |
| | |