| 2020-06-02 11:34:02 | 3RD REVIEW FBC-2017 MECHANICAL |
| | PERMIT- 19120804 |
| | 6/2/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M6.1: THE OUTSIDE AIR CALCULATION SCHEDULE |
| | INDICATING A BEDROOM, STORAGE ROOM ETC. DOES NOT MATCH |
| | THE REVISED ARCHITECTURAL FLOOR PLANS AND AREA |
| | CALCULATIONS- PLEASE CORRECT- TABLE 403.3.1.1 FBC M. |
| | PLEASE PROVIDE ROOM IDENTIFICATIONS ON THE MECHANICAL |
| | FLOOR PLANS TO MATCH WITH THE NEW ARCHITECTURAL PLANS- |
| | SECTION 107.2.1 WPB. |
| | |
| | 2) AS PREVIOUSLY REQUESTED, PLEASE PROVIDE THE CORRECT |
| | ADDRESS ON PAGE 2 OF THE ENERGYGAUGE COMPLIANCE REPORT. |
| | PLEASE NOTE THAT THE ADDRESS ON THE APPLICATION, THE |
| | PLANS, AND THE ENERGY FORM DO NOT MATCH- SECTION 105.3 |
| | WPB. CORRECT THE 2715 PINEWOOD ADDRESS ON THE FORM TO |
| | MATCH WITH THE 2723 PINEWOOD ADDRESS ON THE PLANS. |
| | |
| | 3) COMMENT #4 FROM THE 2ND REVIEW- FAILED. THE $9,500 |
| | JOB VALUE ON THE APPLICATION IS VERY LOW FOR THE SCOPE |
| | OF THE PROJECT. TOTAL VALUE SHALL INCLUDE THE COSTS OF |
| | LABOR, MATERIALS, EQUIPMENT, APPLIANCES, FIXTURES ETC. |
| | FOR ALL TRADES INCLUDING STRUCTURAL, ELECTRIC, |
| | PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE |
| | WORK, AND SHALL ALSO INCLUDE ARCHITECTURAL AND DESIGN |
| | FEES, MARKETING COSTS, AND OVERHEAD AND PROFIT. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS- SECTION 109.3 WPB. |
| | |
| | THE SUBMITTED COST BREAKDOWN INDICATING $10,000.00 COST |
| | FOR THE HVAC APPEARS TO BE A VERY LOW VALUE FOR THE NEW |
| | SYSTEMS AND COMPONENTS BEING INSTALLED AS LISTED BELOW. |
| | PLEASE PROVIDE A COPY OF THE CONTRACT AND/OR ESTIMATES |
| | AND INVOICES VERIFYING THE TOTAL COST OF LABOR, |
| | MATERIALS AND EQUIPMENT FOR THE PROPOSED PROJECT. |
| | |
| | A) MITSUBISHI 8-TON VARIABLE REFRIGERANT SYSTEM- |
| | INCLUDING CU-1 & 2, AND 11 ROOM AIRHANDLERS. |
| | B) TRANE 4-TON 100% OUTSIDE AIR SYSTEM. |
| | C) EF- 1 &2 AND EXHAUST DUCTS |
| | D) GRAVITY VENTILATOR ON THE ROOF |
| | E) FIRST AND SECOND FLOOR SUPPLY AND RETURN DUCTWORK. |
| | F) VRF REFRIGERANT LINES |
| | G) CONDENSATE PIPING. |
| | H) FIRE DAMPERS, LOUVERS, MOTORIZED DAMPER, |
| | THERMOSTATS, HUMIDISTATS ETC. |
| | I) ELECTRONIC CONTROLS FOR THE VRF AND SYSTEMS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |