| 2020-03-11 10:53:12 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19120804 |
| | 3/11/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) M6.1: THE O/A CALCULATION SCHEDULE IS INDICATING 12 |
| | SQ. FT. FOR STORAGE WHICH IS NOT CONSISTENT WITH THE |
| | FLOOR PLANS AND THE SQUARE FOOTAGE SHOWN IN THE |
| | OCCUPANCY CALCS ON SHEET A1.0- TABLE 403.3.1.1. FBC M. |
| | |
| | 2) M7.1: INDICATE THE TYPE AND SIZE OF ANCHORS FOR |
| | ATTACHING THE CONDENSER BRACKETS TO THE SLAB- SECTION |
| | 301.15 FBC M. |
| | |
| | 3) PROVIDE THE CORRECT ADDRESS ON PAGE 2 OF THE |
| | ENERGYGAUGE COMPLIANCE REPORT. PLEASE NOTE THAT THE |
| | ADDRESS ON THE APPLICATION, THE PLANS, AND THE ENERGY |
| | FORM DO NOT MATCH- SECTION 105.3 WPB. |
| | |
| | 4) THE $9,500 JOB VALUE ON THE APPLICATION IS VERY LOW |
| | FOR THE SCOPE OF THE PROJECT. TOTAL VALUE SHALL INCLUDE |
| | THE COSTS OF LABOR, MATERIALS, EQUIPMENT, APPLIACES, |
| | FIXTURES ETC. FOR ALL TRADES INCLUDING STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, AND SHALL ALSO INCLUDE |
| | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, AND |
| | OVERHEAD AND PROFIT. VALUATION REFERENCES MAY INCLUDE |
| | THE LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION COST |
| | ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS |
| | PUBLISHED BY INTERNATIONAL CODE CONGRESS- SECTION 109.3 |
| | WPB. |
| | |
| | 5) P2.2: SHOW THE OAHU CONDENSATE PIPE AND DISCHARGE |
| | LOCATION- SECTION 307.2.1 FBC M. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK ?VOID? OR OLD ON THEM. PLEASE |
| | RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. |
| | THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |