| Date |
Text |
| 2020-01-15 12:03:27 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A 1.0 - WHAT IS THE HAZARD OF CONTENTS & |
| | CLASSIFICATION OF HAZARD PER NFPA 101, CH 6 OCCUPANCY |
| | CLASSIFICATION. |
| | |
| | PER NFPA 101, CH 42 & CH 6 |
| | |
| | 42.1.5 CLASSIFICATION OF HAZARD OF CONTENTS. |
| | 42.1.5.1 CONTENTS OF STORAGE OCCUPANCIES SHALL BE |
| | CLASSIFIED AS |
| | LOW HAZARD, ORDINARY HAZARD, OR HIGH HAZARD IN |
| | ACCORDANCE WITH |
| | SECTION 6.2, DEPENDING ON THE QUANTITY AND CHARACTER OF |
| | THE |
| | MATERIALS STORED, THEIR PACKAGING, AND OTHER FACTORS. |
| | 42.1.5.2 HAZARDOUS MATERIALS THAT EXCEED THE MAXIMUM |
| | ALLOWABLE |
| | QUANTITIES (MAQ) AS PERMITTED IN THE FIRE CODE SHALL BE |
| | CLASSIFIED |
| | AS HIGH-HAZARD CONTENTS. |
| | |
| | 6.2 HAZARD OF CONTENTS. |
| | 6.2.1 GENERAL. |
| | 6.2.1.1 FOR THE PURPOSE OF THIS CODE, THE HAZARD OF |
| | CONTENTS SHALL |
| | BE THE RELATIVE DANGER OF THE START AND SPREAD OF FIRE, |
| | THE DANGER OF |
| | SMOKE OR GASES GENERATED, AND THE DANGER OF EXPLOSION |
| | OR OTHER |
| | OCCURRENCE POTENTIALLY ENDANGERING THE LIVES AND SAFETY |
| | OF THE |
| | OCCUPANTS OF THE BUILDING OR STRUCTURE. |
| | 6.2.1.2 HAZARD OF CONTENTS SHALL BE CLASSIFIED BY THE |
| | REGISTERED |
| | DESIGN PROFESSIONAL (RDP) OR OWNER AND SUBMITTED TO THE |
| | AUTHORITY HAVING JURISDICTION FOR REVIEW AND APPROVAL |
| | ON THE BASIS |
| | OF THE CHARACTER OF THE CONTENTS AND THE PROCESSES OR |
| | OPERATIONS |
| | CONDUCTED IN THE BUILDING OR STRUCTURE. |
| | 6.2.1.3* FOR THE PURPOSE OF THIS CODE, WHERE DIFFERENT |
| | DEGREES OF |
| | HAZARD OF CONTENTS EXIST IN DIFFERENT PARTS OF A |
| | BUILDING OR STRUCTURE, |
| | THE MOST HAZARDOUS SHALL GOVERN THE CLASSIFICATION, |
| | UNLESS |
| | HAZARDOUS AREAS ARE SEPARATED OR PROTECTED AS SPECIFIED |
| | IN SECTION |
| | 8.7 AND THE APPLICABLE SECTIONS OF CHAPTERS 11 THROUGH |
| | 43. |
| | |
| | 6.2.2 CLASSIFICATION OF HAZARD OF CONTENTS. |
| | 6.2.2.1* GENERAL. THE HAZARD OF CONTENTS OF ANY |
| | BUILDING OR |
| | STRUCTURE SHALL BE CLASSIFIED AS LOW, ORDINARY, OR HIGH |
| | IN |
| | ACCORDANCE WITH 6.2.2.2, 6.2.2.3, AND 6.2.2.4. |
| | 6.2.2.2* LOW HAZARD CONTENTS. LOW HAZARD CONTENTS SHALL |
| | BE |
| | CLASSIFIED AS THOSE OF SUCH LOW COMBUSTIBILITY THAT NO |
| | SELFPROPAGATING |
| | FIRE THEREIN CAN OCCUR. |
| | 6.2.2.3* ORDINARY HAZARD CONTENTS. ORDINARY HAZARD |
| | CONTENTS SHALL |
| | BE CLASSIFIED AS THOSE THAT ARE LIKELY TO BURN WITH |
| | MODERATE RAPIDITY OR |
| | TO GIVE OFF A CONSIDERABLE VOLUME OF SMOKE. |
| | 6.2.2.4* HIGH HAZARD CONTENTS. HIGH HAZARD CONTENTS |
| | SHALL BE |
| | CLASSIFIED AS THOSE THAT ARE LIKELY TO BURN WITH |
| | EXTREME RAPIDITY OR FROM |
| | WHICH EXPLOSIONS ARE LIKELY. (FOR MEANS OF EGRESS |
| | REQUIREMENTS, SEE |
| | SECTION 7. 11.) |
| | |
| | |
| | 2) SHEET A 4.0 - THE 2ND FLOOR EXIT STAIRWAY IS LOCATED |
| | NEAR AN EXIT DOOR/OPENING AT THE BOTTOM. |
| | |
| | PER NFPA 101, CH 42 AND CH 7 |
| | |
| | 42.2 MEANS OF EGRESS REQUIREMENTS. |
| | 42.2.1 GENERAL. |
| | 42.2.1.1 EACH REQUIRED MEANS OF EGRESS SHALL BE IN |
| | ACCORDANCE |
| | WITH THE APPLICABLE PORTIONS OF CHAPTER 7. |
| | |
| | 7.2.2.6.3 SEPARATION AND PROTECTION OF OUTSIDE STAIRS. |
| | 7.2.2.6.3.1* OUTSIDE STAIRS SHALL BE SEPARATED FROM THE |
| | INTERIOR OF THE |
| | BUILDING BY CONSTRUCTION WITH THE FIRE RESISTANCE |
| | RATING REQUIRED FOR |
| | ENCLOSED STAIRS WITH FIXED OR SELF-CLOSING OPENING |
| | PROTECTIVES, |
| | EXCEPT AS FOLLOWS: |
| | (1) OUTSIDE STAIRS SERVING AN EXTERIOR EXIT ACCESS |
| | BALCONY THAT HAS |
| | TWO REMOTE OUTSIDE STAIRWAYS OR RAMPS SHALL BE |
| | PERMITTED TO BE |
| | UNPROTECTED. |
| | (2) OUTSIDE STAIRS SERVING TWO OR FEWER ADJACENT |
| | STORIES, INCLUDING |
| | THE STORY WHERE THE EXIT DISCHARGES, SHALL BE PERMITTED |
| | TO BE |
| | UNPROTECTED WHERE THERE IS A REMOTELY LOCATED SECOND |
| | EXIT. |
| | (3) IN EXISTING BUILDINGS, EXISTING OUTSIDE STAIRS |
| | SERVING THREE OR |
| | FEWER ADJACENT STORIES, INCLUDING THE STORY WHERE THE |
| | EXIT |
| | DISCHARGES, SHALL BE PERMITTED TO BE UNPROTECTED WHERE |
| | THERE IS |
| | A REMOTELY LOCATED SECOND EXIT. |
| | (4) THE FIRE RESISTANCE RATING OF A SEPARATION |
| | EXTENDING 10 FT (3050 |
| | MM) FROM THE STAIRS SHALL NOT BE REQUIRED TO EXCEED 1 |
| | HOUR |
| | WHERE OPENINGS HAVE A MINIMUM ?-HOUR FIRE PROTECTION |
| | RATING. |
| | (5) OUTSIDE STAIRS IN EXISTING BUILDINGS PROTECTED |
| | THROUGHOUT BY AN |
| | APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH SECTION 9.7 SHALL BE PERMITTED TO BE |
| | UNPROTECTED. |
| | 7.2.2.6.3.2 WALL CONSTRUCTION REQUIRED BY 7.2.2.6.3.1 |
| | SHALL EXTEND AS |
| | FOLLOWS: |
| | (1) VERTICALLY FROM THE FINISHED GROUND LEVEL TO A |
| | POINT 10 FT (3050 |
| | MM) ABOVE THE TOPMOST LANDING OF THE STAIRS OR TO THE |
| | ROOFLINE, |
| | WHICHEVER IS LOWER |
| | (2) HORIZONTALLY FOR NOT LESS THAN 10 FT (3050 MM) |
| | |
| | THE DOOR IS WITHIN THE 10FT. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 3) SHEET A 4.0 - THERE IS ONLY ONE EXIT INDICATED FORM |
| | THE 2ND FLOOR |
| | |
| | PER NFPA 101 CH 42 AND CH 7 |
| | |
| | 42.2.4 NUMBER OF MEANS OF EGRESS. THE NUMBER OF MEANS |
| | OF |
| | EGRESS SHALL COMPLY WITH 42.2.4.1 THROUGH 42.2.4.3. |
| | (SEE ALSO |
| | SECTION 7.4.) |
| | 42.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL COMPLY |
| | WITH ANY OF |
| | THE FOLLOWING: |
| | (1) IN LOW HAZARD STORAGE OCCUPANCIES, A SINGLE MEANS |
| | OF EGRESS |
| | SHALL BE PERMITTED FROM ANY STORY OR SECTION. |
| | (2) IN ORDINARY HAZARD STORAGE OCCUPANCIES, A SINGLE |
| | MEANS OF |
| | EGRESS SHALL BE PERMITTED FROM ANY STORY OR SECTION, |
| | PROVIDED |
| | THAT THE EXIT CAN BE REACHED WITHIN THE DISTANCE |
| | PERMITTED AS A |
| | COMMON PATH OF TRAVEL. |
| | (3) ALL BUILDINGS OR STRUCTURES NOT COMPLYING WITH |
| | 42.2.4.1(1) OR |
| | 42.2.4.1(2) AND USED FOR STORAGE, AND EVERY SECTION |
| | THEREOF |
| | CONSIDERED SEPARATELY, SHALL HAVE NOT LESS THAN TWO |
| | SEPARATE |
| | MEANS OF EGRESS AS REMOTELY LOCATED FROM EACH OTHER AS |
| | PRACTICABLE. |
| | |
| | 42.2.6* TRAVEL DISTANCE TO EXITS. TRAVEL DISTANCE, |
| | MEASURED IN |
| | ACCORDANCE WITH SECTION 7.6, SHALL NOT EXCEED THAT |
| | PROVIDED BY |
| | TABLE 42.2.6. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS OF LOW HAZARD OR |
| | INDICATE THE TRAVEL DISTANCES AS LESS THAN 50 FT |
| | |
| | |
| | |
| | 4) SHEET A 4.0 - THERE ARE NO INDICATIONS OF HOW THE |
| | STORAGE WILL BE STORED OR IF RACKS WILL BE PROVIDED. |
| | |
| | PLEASE PROVIDE ALL APPLICABLE DETAILS RELATED TO HOW |
| | THE COMMODITY WILL BE STORED AISL;E/FLOOR LAYOUTS FOR |
| | EACH ROOM, AND RACK INFORMATION, INCLUDING PALLET |
| | TYPES, COMMODITY TYPE, WRAPPING TYPES, SHELLVING TYPES, |
| | HEIGHTS, WEIGHT LIMITS, ETC, FOR REVIEW PURPOSES. |
| | |
| | RACKS SHALL BE INSTALLED UNDER SEPARATE PERMIT AND SHOP |
| | DRAWINGS. |
| | |
| | |
| | |
| | 5) SHEET 4.0 - THERE ARE INDICATION OF DEAD STORAGE, |
| | WITH NO DEFINITION, ADDITIONALLY, WHAT IS THE PROPOSED |
| | WEIGHT LIMIT OF THE FLOORING OF THE 2ND FLOOR AND HOW |
| | WILL IT BE MONITORED? |
| | |
| | PLEASE PROVIDE THE DEAD STORAGE DEFINITION AND ALL |
| | APPLICABLE DETAILS RELATED TO STORAGE INCULDING THE 2ND |
| | FLOOR. |
| | |
| | ANY PROPOSED RACKS IN THE STORAGE AREA SHALL BE |
| | INSTALLED UNDER SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |